23. Hook spring on handle ear and Network Protector bracket.
24. Rotate the handle to AUTO position while applying inward pressure.
CAUTION
This step winds the spring under compression and has
considerable stored energy. Use caution when installing
the assembly.
25. It is recommended to use a pair of Vice Grip Pliers to hold the handle in place while
installing the setscrews.