5   Installation

Installation and Operating Instructions  Web-Controller

   40071860236 (E)   February 2019   www.eaton.com

System button 

3

The system button enables the  Web-Controller to be 

connected to a PC. If pressed for ~ 3 seconds, the green USB2 

LED turns on and an external storage from Windows will be 

detected. An access via PC software will be possible now. To 

remove the controller the following steps are required:
1.  Remove external hard drive via windows
2.  Press system button for 3 seconds, green USB2 LED will 

turn off

Fig . 3 .   Connecting the controller to a laptop with  

PC-Software via USB A-B

Reset button 

3

The reset button resets the  Web-Controller (not fac-

tory default). For this purpose, the button must be pressed 

and held for >1 second.

5 .2 .3   Connections

230 V/AC

 

6

Connection terminals for power supply 230 V/ AC with 50/60 

Hz. 

Bus: 

7

The Web-Controller is compatible to the old CGLine technlogy. 

If one or more CGLine luminaires are connected, the CGLine 

compatible mode is active. Following luminaires can be con-

nected:

Table 2.  Max. number of luminaires to be connected

Line No.

CGLine

4 lines

2 lines

1

100

200

400

2

100

200

400

3

100

200

-

4

100

200

-

Total

400

800

800

Polarity D1/D2 to the luminaires must not be observed. Cable 

routing for CGLine bus: 2-core bus line, unshielded, free bus 

topology possible.

Table 3 .  Cable length/line

Cross-section

Length

Total lines

0.5 qmm

260 m

660 m

1.0 qmm

520 m

1320 m

1.5 qmm

800 m

2000 m

Table 4.  Electrical data/line

Power supply bus

25 V

Max. permissible voltage drop 6 V
Bus current

300 mA

NOTE

In case of a communication failure with a luminaire please 

check the following:
1.  Check the proper connection of the bus line at the lumi-

naire’s connector

2.  Check the correct bus voltage at the luminaire (see table 4.)
3.  In case the voltage is correct and the communication failure 

still exists: Check the bus line resistance which shouldn’t 

exceed 32 Ohm. For that please disconnect the relevant line 

from the web-controller, apply a short cut between the bus 

contacts at the affected luminaire and measure the resis-

tance at the other end of the line.

RS485 

8

No function. Only for french market. 

LAN connection

 

9

Ethernet connection via RJ45 socket. A LAN patch cable must 

be used for direct connection of a PC/notebook. 

Blocking input (S1/S2): 

All connected luminaires can be blocked via the blocking 

input, meaning the luminaires are switched off and the emer-

gency light function deactivated, for example for idle operat-

ing times.
Connection is via a key switch or relay (e.g. alarm system). To 

guarantee reliable operation from short-circuit or interruption 

of the blocking line, this input is equipped with differential 

loop monitoring (static current), meaning a 1kOhm resistance 

must be integrated for blocking that defines the static current.

Connection example:

With closer contact

S1 CGLine

S2 Interface

With opener contact

Содержание CGLine+ Web-Controller

Страница 1: ...Installation and Operating Instructions CGLine Web Controller Target group Electrical specialists CGLine Web Controller...

Страница 2: ...EENS 13 7 1 Home start screen 13 7 2 Start screen after registration 14 7 3 Overview of all faulty luminaires complete overview 15 7 4 Overview of all faulty luminaires for each zone 16 7 5 Overview o...

Страница 3: ...lines with max 200 luminaires each or 2 lines with max 400 luminaires each only with homogeneous installation of CGLine luminaires CGVision software Configuration and full visualisation of 32 x 800 N...

Страница 4: ...policies O O Restrict Network Access Ideally CGLine Web Controller should be installed on a segregated network However when the CGLine Web Controller is connected to a wider network make sure that the...

Страница 5: ...technical regulations when setting up and operating electrical operating equipment 5 1 Assembly Observe impermissible temperatures at the installation loca tion during mounting The permissible ambient...

Страница 6: ...ctional method O O Press the service pin 1 sec but 3 sec function test started for all luminaires O O Press the service pin 6 sec only new luminaires search started 1 6 7 8 9 10 2 3 4 5 3 Push buttons...

Страница 7: ...Table 3 Cable length line Cross section Length Total lines 0 5 qmm 260 m 660 m 1 0 qmm 520 m 1320 m 1 5 qmm 800 m 2000 m Table 4 Electrical data line Power supply bus 25 V Max permissible voltage drop...

Страница 8: ...tandard PC Controller functions can be programmed via the PC and a configuration software e g luminaire configurations The PC configuration software is available optionally 6 First commissioning and m...

Страница 9: ...displayed Mark the entry Internet protocol version 4 1 then continue with Properties 2 Usually the network card is on DHCP i e Automatically reference IP address Modify the entry to Use the following...

Страница 10: ...o the address bar The start screen of the CGLine Web Controller opens The screen shows an over view of the installed CGLine system with sum status information To have access to the submenus a login 1...

Страница 11: ...tion 1 It is possible to change the network settings 1 6 5 Modifying of the language date and time To change the language to English please click on Configuration 1 in the register General 2 The langu...

Страница 12: ...via the names is possible The CGLine Web Controller is supplied with a factory set static IP address of 192 168 1 200 3 Operation via DHCP is possible but in this case it is recommended to select sta...

Страница 13: ...s User Admin Password EATON User User Password GUEST 1 The Admin Account allows full access to the CGLine Web Controller e g start function test The User account allows only access for monitoring the...

Страница 14: ...Yellow min 1 luminaire faulty O O Red min 3 luminaires faulty e g lamp failure After the login the navigation menu appears on the left side 1 O O Home The start screen is accessed via Home at any time...

Страница 15: ...ible to enter to the building layout picture if it is pre The menu Oveview 1 and the tab Overview luminaire failure 2 display all luminaires with a fault 3 O O L line no 1 4 O O Z zone 2 16 O O B lumi...

Страница 16: ...er 40071860236 E February 2019 www eaton com 7 4 Overview of all faulty luminaires for each zone All luminaires with a fault in a zone are displayed in the Overview menu 1 and the Zone tab 2 Via the d...

Страница 17: ...erview luminaires 2 shows all installed luminaires on the CGLine Web Controller 1 2 7 6 Information information text of the luminaires This screen shows the name with max 20 characters and information...

Страница 18: ...f luminaires addresses For changing the configuration of luminaires addresses please follow the steps below 1 Click on the tab Luminaires The table with all the luminaires installed appears 2 Click on...

Страница 19: ...uration tests are aborted O O Switch maintained mode ON OFF Luminaires in main tained mode L applied can be switched ON or OFF if luminaire supports this function O O Update luminaire status Actualisi...

Страница 20: ...st times On the Test tab 2 in the configuration menu 1 it is possible to determine start times for a function test and duration test for up to 8 groups It is also possible to set a test interval via w...

Страница 21: ...mode luminaires of the line as long as the input is active O O Start function test With positive pulse starts the function test with all luminaires O O Stop FT DT Interrupts a duration test or functi...

Страница 22: ...ally correct it is necessary after the commissioning to correctly set the date and 2 1 4 5 3 7 13 Network settings Follwing settings are possible O O DHCP Dynamic Host Control Protocol if a DHCP is in...

Страница 23: ...plete logbook is downloadable via log book dat This file is only usable with the CGLine PC software see manual CGLine PC software The CGLine Web Controller contains an integrated e mail client 1 that...

Страница 24: ...layouts of the building or areas It is possible to import up to 30 building layout plans with max 200 luminaires each The colour of the luminaire shows the status e g red luminaire failure To use this...

Страница 25: ...ding layouts can displayed now by the folder List of building layouts 1 With click on the name of the layout which is dis played as hyperlink with xml extension 2 the lay out can load from the con tro...

Страница 26: ...n there is a search func tion 1 2 This enables quickly finding any defective luminaires in a building To find a luminaire in the layout plan the line the zone and the luminaire to address can be selec...

Страница 27: ...e entered here After con firming via Add the devices are automatically created A device can be deleted from the list again via Delete 3 3 1 2 7 24 Overview all Web Controller With several installed CG...

Страница 28: ...ght solution for the application But decision makers demand more than just innovative products They turn to Eaton for an unwavering commitment to personal support that makes customer success a top pri...

Отзывы: