4

2   Safety notes

Installation and Operating Instructions  Web-Controller

   40071860236 (E)   February 2019   www.eaton.com

2   Safety notes

 CAUTION 

 

n

The CGLine web interface must be operated in an undam-

aged and functional state.

 

n

When carrying out maintenance work to the device the 

device must be switched off. 

 

n

When carrying out device maintenance, observe national 

safety and accident prevention regulations and the safety 

notes in the operating instructions below designated with 

.

3   Conformity to standards

Compliant with: EN 60950-1. Developed, manufactured and 

tested according to DIN EN ISO 9001.  

 

CYBERSECURITY

This chapter provides guidelines to securely deploy the 

 Web-Controller and minimize the cybersecurity risk 

to the installer system.

 

n

Asset identification and inventory: Ensure that the  

Web-Controller is labelled and inventoried using the Part 

num¬ber and Mac address printed on the product label, 

and also the IP address configured during the installation of 

the material and actual firmware version. 

 

n

Restrict Physical access: Ensure that physical access to the 

 Web-Controller is restricted only to authorized 

user(s).  Web-Controller supports the physical 

access ports RJ-45, USB that can be used to tamper the 

device. Access to these ports should be restricted to autho-

rized personnel only. Secure the facility and equipment 

rooms or closets with access control mechanisms such as 

locks, entry card readers, guards, man traps, CCTV, etc. as 

appropriate. Monitor and log the access at all times. Before 

connecting any portable device through a USB port or SD 

card slot, scan the device to prevent unauthorized access.

 

n

Restrict Logical access: Access to ‘Admin’ & ‘Service’ user 

accounts should be restricted to authorized personnel only 

as system configuration can be tampered by abusing these 

accounts. Ensure password length, complexity and expira-

tion requirements are appropriately set, particularly for all 

administrative accounts (e.g., minimum 10 characters, mix 

of upper- and lower-case and special characters, and expire 

every 90 days, or otherwise in accordance with your organi-

zation’s policies).

 

n

Restrict Network Access: Ideally,  Web-Controller 

should be installed on a segregated network. However, 

when the  Web-Controller is connected to a wider 

network, make sure that the IP address and MAC address 

are filtered at the router side, or using a firewall. In addition 

to this, open only the ports used by the  Web-

Controller (SMTP as configured, 587 for SMTPS, 443 for 

HTTPS, and 5000 for OPC communication).

 

n

Logging and event management: Make sure you log all rel-

evant system and application events, including all admin-

istrative and maintenance activities. Logs should be pro-

tected from tampering and other risks to their integrity (for 

example, by restricting permissions to access and modify 

logs, transmitting logs to a security information and event 

management system, etc.). Ensure that logs are retained for 

a reasonable and appropriate length of time. Review the 

logs regularly. The frequency of review should be reason-

able, taking into account the sensitivity and criticality of 

the  Web-Controller and any data it processes. The 

details how to export the logs are defined in chapter 7.14.

 

n

Secure maintenance: In case the firmware of the device 

needs to be updated, you will be contacted by your Eaton 

local support.

 

n

Business continuity / cybersecurity disaster recovery: Eaton 

recommends incorporating  Web-Controller into 

the organization’s business continuity and disaster recovery 

plans.  Organizations should establish a Business Continuity 

Plan and a Disaster Recovery Plan and should periodically 

review and, where possible, exercise these plans. As part of 

the plan, important device data should be backed up and 

securely stored, including the current configuration and 

documentation of the current permissions / access controls, 

if not backed up as part of the configuration. The  

PC can be used to save the configuration of a  

Web-Controller using the “save file” button in the main 

page. 

 

n

Decommissioning: It is a best practice to purge data before 

disposing of any device containing data. Guidelines for 

decommissioning are provided in NIST SP 800-88. To ensure 

data is unrecoverable,  Web-Controller must be 

securely destroyed. Method of destruction include disinte-

gration, Incineration, Pulverization, or Melting of the elec-

tronic inside the  Web-Controller.

Содержание CGLine+ Web-Controller

Страница 1: ...Installation and Operating Instructions CGLine Web Controller Target group Electrical specialists CGLine Web Controller...

Страница 2: ...EENS 13 7 1 Home start screen 13 7 2 Start screen after registration 14 7 3 Overview of all faulty luminaires complete overview 15 7 4 Overview of all faulty luminaires for each zone 16 7 5 Overview o...

Страница 3: ...lines with max 200 luminaires each or 2 lines with max 400 luminaires each only with homogeneous installation of CGLine luminaires CGVision software Configuration and full visualisation of 32 x 800 N...

Страница 4: ...policies O O Restrict Network Access Ideally CGLine Web Controller should be installed on a segregated network However when the CGLine Web Controller is connected to a wider network make sure that the...

Страница 5: ...technical regulations when setting up and operating electrical operating equipment 5 1 Assembly Observe impermissible temperatures at the installation loca tion during mounting The permissible ambient...

Страница 6: ...ctional method O O Press the service pin 1 sec but 3 sec function test started for all luminaires O O Press the service pin 6 sec only new luminaires search started 1 6 7 8 9 10 2 3 4 5 3 Push buttons...

Страница 7: ...Table 3 Cable length line Cross section Length Total lines 0 5 qmm 260 m 660 m 1 0 qmm 520 m 1320 m 1 5 qmm 800 m 2000 m Table 4 Electrical data line Power supply bus 25 V Max permissible voltage drop...

Страница 8: ...tandard PC Controller functions can be programmed via the PC and a configuration software e g luminaire configurations The PC configuration software is available optionally 6 First commissioning and m...

Страница 9: ...displayed Mark the entry Internet protocol version 4 1 then continue with Properties 2 Usually the network card is on DHCP i e Automatically reference IP address Modify the entry to Use the following...

Страница 10: ...o the address bar The start screen of the CGLine Web Controller opens The screen shows an over view of the installed CGLine system with sum status information To have access to the submenus a login 1...

Страница 11: ...tion 1 It is possible to change the network settings 1 6 5 Modifying of the language date and time To change the language to English please click on Configuration 1 in the register General 2 The langu...

Страница 12: ...via the names is possible The CGLine Web Controller is supplied with a factory set static IP address of 192 168 1 200 3 Operation via DHCP is possible but in this case it is recommended to select sta...

Страница 13: ...s User Admin Password EATON User User Password GUEST 1 The Admin Account allows full access to the CGLine Web Controller e g start function test The User account allows only access for monitoring the...

Страница 14: ...Yellow min 1 luminaire faulty O O Red min 3 luminaires faulty e g lamp failure After the login the navigation menu appears on the left side 1 O O Home The start screen is accessed via Home at any time...

Страница 15: ...ible to enter to the building layout picture if it is pre The menu Oveview 1 and the tab Overview luminaire failure 2 display all luminaires with a fault 3 O O L line no 1 4 O O Z zone 2 16 O O B lumi...

Страница 16: ...er 40071860236 E February 2019 www eaton com 7 4 Overview of all faulty luminaires for each zone All luminaires with a fault in a zone are displayed in the Overview menu 1 and the Zone tab 2 Via the d...

Страница 17: ...erview luminaires 2 shows all installed luminaires on the CGLine Web Controller 1 2 7 6 Information information text of the luminaires This screen shows the name with max 20 characters and information...

Страница 18: ...f luminaires addresses For changing the configuration of luminaires addresses please follow the steps below 1 Click on the tab Luminaires The table with all the luminaires installed appears 2 Click on...

Страница 19: ...uration tests are aborted O O Switch maintained mode ON OFF Luminaires in main tained mode L applied can be switched ON or OFF if luminaire supports this function O O Update luminaire status Actualisi...

Страница 20: ...st times On the Test tab 2 in the configuration menu 1 it is possible to determine start times for a function test and duration test for up to 8 groups It is also possible to set a test interval via w...

Страница 21: ...mode luminaires of the line as long as the input is active O O Start function test With positive pulse starts the function test with all luminaires O O Stop FT DT Interrupts a duration test or functi...

Страница 22: ...ally correct it is necessary after the commissioning to correctly set the date and 2 1 4 5 3 7 13 Network settings Follwing settings are possible O O DHCP Dynamic Host Control Protocol if a DHCP is in...

Страница 23: ...plete logbook is downloadable via log book dat This file is only usable with the CGLine PC software see manual CGLine PC software The CGLine Web Controller contains an integrated e mail client 1 that...

Страница 24: ...layouts of the building or areas It is possible to import up to 30 building layout plans with max 200 luminaires each The colour of the luminaire shows the status e g red luminaire failure To use this...

Страница 25: ...ding layouts can displayed now by the folder List of building layouts 1 With click on the name of the layout which is dis played as hyperlink with xml extension 2 the lay out can load from the con tro...

Страница 26: ...n there is a search func tion 1 2 This enables quickly finding any defective luminaires in a building To find a luminaire in the layout plan the line the zone and the luminaire to address can be selec...

Страница 27: ...e entered here After con firming via Add the devices are automatically created A device can be deleted from the list again via Delete 3 3 1 2 7 24 Overview all Web Controller With several installed CG...

Страница 28: ...ght solution for the application But decision makers demand more than just innovative products They turn to Eaton for an unwavering commitment to personal support that makes customer success a top pri...

Отзывы: