In the menu “Commands”
1
all commands can be
sent to single lumi-
naires. It is possible to send
the commands to all lumi-
naires or to one line, zone or
even to a single luminaire.
2
:
Status display of the total
system and the pot.-free IN/
OUT puts.
The following commands
3
can be set:
n
Block: Emergency light function and maintained mode are
deactivated, e.g. during idle operating times
n
Rest mode: During a mains failure (luminaires are in emer-
gency mode), the rest mode will switch OFF the luminaires.
If mains return, the luminaires will go back in normal mode.
To the next mains failure, the luminaires switch again to
emergency mode.
n
Release / Relight: Release of the blocking or rest mode
function
n
Start functional test: Specified luminaires start a function
test
n
Start duration test: Specified luminaires start a battery
duration test
n
Stop FT / DT: Function tests or duration tests are aborted
n
Switch maintained mode ON / OFF: Luminaires in main-
tained mode (L’ applied) can be switched ON or OFF (if
luminaire supports this function)
n
Update luminaire status: Actualisiation of the luminaire sta-
tus of all luminaires
n
Update luminaire type: Actualisation of luminaire type
information
7 .8 Switching command screen
1
2
3
4
n
Search all lamp: Completely new luminaire search – cau-
tion: old configurations are overwritten. All luminaires will
be addressed with a logical address from 1 up to 200 or 1
up to 400.
n
Search new lamp: Starts a luminaire search and only
adds newly found luminaires. All new luminaires will be
addressed with a logical address from last existing lumi-
naire up to 200 or up to 400.
n
Search initialized lamp: Already addressed luminaires keeps
their addresses after search
n
Load config PC soft: Load a configuration which was cre-
ated by the PC software. The config file must have
the filename „config.xml
Selection of luminaires to be controlled
4
:
n
Line: Selection of luminaire lines 1 to 4
n
Zone: Selection of luminaire zone 2 to 16
n
Luminaire: Selection of single luminaires in the line and
zone
n
If “All” is selected: Command applies to all luminaires