31
4 Construction and Function
Mounting and Operating Instructions CEAG Central Battery System ZB-S 40071860179 (L) November 2018 www.ceag.de
Standard PC with CEAG software
for the ZB-S system
Standard printer for printing off the test log stored on the
memory card or a system configuration
O
O
a usual personal computer (PC) and
O
O
CEAG-software for the system ZB-S.
Communication and control
O
O
Data exchange
with installed CG-S components and CG-S-compatible
ballasts (using the cables of the final circuits)
O
O
RS485 bus
allows data to be exchanged with external modules
(DLS/3PH-bus-modules or TLS-bus-modules, (RS485 port
on the control module, up to 25 devices).
O
O
External CG-S bus port
(CEAG bus protocol) for data exchange with BMS.
Data Exchange and Storage
O
O
Internal:
with non-volatile memory in the CU CG-S control module
O
O
External:
with a memory card reader, type of the uses memory
card:
SD-card / CEAG part no. 400 71 347 911 (preprogrammed)
O
O
SD-adapter
enables data exchange and saving with usual PC under
the CEAG-Software for the system ZB-S
Connections
O
O
3-tier-installation terminal with tension spring all
connections are taken out to a 3-tier-installation terminal
with tension spring, see page 28: detail view and
Appendix A: „Connection Assignment“
O
O
Pluggable screw terminal block at the device enables a
simple assembly and disassembly.
O
O
Bus cables 4 x 2 x 0,8 mm, type: JY(ST)Y, Twistet Pair
screended (minimum requirement).
O
O
Connection for zero-potential signal contacts, 24 V 0.5
A:
3 relays with common potential, 1 x switching contact
each. One or several from 11 different messages can
be assigned to each zero-potential contact. Freely
programmable, DIN VDE 0100, Section 718 specification