8 Operating
Mounting and Operating Instructions CEAG Central Battery System ZB-S 40071860179 (L) November 2018 www.ceag.de
Overview:
Main menu
Test & status menu
Block & reset alarms
Basic settings
DLS/TLS Setup
Circuit setup
Luminaire setup
Logbooksetup
Send ServicePinMsg
Menu 5
Deactivate module
Search ext. modules
Text assignment
Monitoring mode
DLS/TLS-Assignment
Get new rated value
Selection of
menu options
with the keys
<ok>:
confirm selec-
tion
<Menu>: can-
cel and return
to the previous
menu (any
changes en-
tered are saved)
<ESC>: cancel
and return to
the previous
menu (any
changes en-
tered are not
saved)
flashing input
prompt
Select line 2 or 4 or the input fields in
line 2 with
Successive selection of subrack/SKU
and circuit with
Changing the circuit name:
– Select line 4 with
– Select the input point with
– All the possible alphanumeric
characters are displayed cycli-
cally with the cursor keys
.
– Once a name has been fully
entered, confirm the entry with
<ok>. The remaining characters
after the current cursor position
are cleared.
Finish and return to Menu 5 with
<Menu>
ote:
N
This menu can be used to assign/
edit circuit names without affect-
ing the configuration.
The procedure is necessary, for
example when the system is first
commissioned or after adding SKU
modules.
Circuit names are stored on the
memory card and displayed in
the LC display menus as opera-
tor help. Text assignments cannot
be made with the CU CG-S if a
memory card is not inserted!
Otherwise, refer to menu
option 4.2
Deactivate module
Search ext. modules
Text assignment
Monitoring mode
DLS/TLS-Assignment
Get new rated value
Menu 5.3:
<ok>
Text assignments
SKU1/8
circuit:2
Type: SKU CG-S 2x3
Circuit name
Menu 5.4:
<ok>
Select line 1, 2, 3 or the input fields in
line 1 with
Successive selection of SKU/output
and (final) circuit with
Line 4 shows the circuit name (see
menu 5.2)
Select the monitoring mode with keys
Finish and return to Menu 5 with
<Menu>
The “CG monitoring” option requires CG-S ballasts/modules and therefore addressable
luminaires from the CEAG range.
For other luminaires, a function test with the “Current value monitoring” option can be
carried out on the basis of the current flow in an entire luminaire circuit (refer to the
settings in “5.5 Learn current values”).
When “Current value monitoring” is selected, line 3 prompts entry of the maximum
deviation (1 ... 20%) from the reference value determined in “5.5 Learn current values”
at which there is still no fault message in a function test.So that the failure of the weak-
est luminaire in a final circuit can be detected, select:
P
min
max. dev. < ––––– x 100(P
min
= Mains connected load of the smallest luminaire)
P
ges
(P
ges
= Mains connected load of all installed luminaires)
Using a SWR150-module differing to this the current value monitoring has to be set to
minimum 15% - acc. to number of type of luminaire and luminous flux.
ote:
N
The above display shows an exam-
ple of the selection of “Current
value monitoring” for circuit 2,
SKU No. 8 on subrack 1.
The following modes can be selected in
line 2:
– CG monitoring
– Current value monitoring
– Reserve circuit
Deactivate module
Search ext. modules
Text assignment
Monitoring mode
DLS/TLS-Assignment
Get new rated value
SKU1/8
circuit:2
Current value monitoring
max. deviation
20%
Circuit name