3 Technical Data / Battery Installation
3.4.4 With battery set 50.4 Ah
For interconnection see chapter „Circuit Diagrams“
ZB-S/1
0C
EURO ZB.1/200K
EURO ZB.1/204K
1
2
3
4
5
Technical D
ata
Type of battery (C10; 1.8 V/Z; +20 °C)
12 V / 50.4 Ah
Rated voltage of all batteries
216 V
Number of all batteries
18 á 12 V
Battery dimensions in mm (L x W x H)
220 x 172 x 235
final pole
F-M6
Supply terminals
max. 35 mm²
W
eight incl. Batteries
495 kg
Dimensions in mm (W x H x D)
800 x 2050 x 400
Order no. batterie bloc
40066070917
Wir
ing Set 4 0071 346 449 included
No.
Length
Number
1
300 mm
12
2
440 mm
3
3
700 mm
2
4
300 mm
1
5
1200 mm
1
3. Battery console
3. Battery console
2. Battery console
2. Battery console
1. Battery console