10
Mounting and Operating Instructions CEAG Battery Cabinets
40071860035 (N) March 2016 www.ceag.de
3 Technical Data / Battery Installation
3.1.5 Standard-Battery Cabinet 53.7 Ah
For interconnection see chapter „Circuit Diagrams“
1
2
3
4
Technical D
ata
Type of battery (C10; 1.8 V/Z; +20 °C)
12 V / 53.7 Ah
Rated voltage of all batteries
216 V
Number of all batteries
18 á 12 V
Battery dimensions in mm (L x W x H)
220 x 172 x 235
final pole
F-M6
Supply terminals
max. 35 mm²
W
eight incl. Batteries
549 kg
Dimensions in mm (W x H x D)
800 x 2050 x 400
Order no. batterie bloc
40066070901
Protection calss
IP 20
Wir
ing Set 4 0071 347 446 included
No.
Length
Number
1
360 mm
13
2
800 mm
4
3
800 mm
1
4
2000 mm
1
Right hinge
Aperture angle 180°
Top view
Base fixing
1. Battery console
1. Battery console
2. Battery console
2. Battery console
3. Battery console
3. Battery console
4. Battery console
4. Battery console
5. Battery console
5. Battery console