14
Mounting and Operating Instructions CEAG Battery Cabinets
40071860035 (N) March 2016 www.ceag.de
3 Technical Data / Battery Installation
3.1.9 Standard-Battery Cabinet 106 Ah
For interconnection see chapter „Circuit Diagrams“
Standard-Battery Cabinet 106 Ah
The bat
tery cabinets 1
06
Ah wil
l
be buil
t
of tw
o paral
lel connec
-
ted cabinets 39.8 and 66.2
Ah
by using t
he bat
tery d
istribut
ion
panel (4007
1360203) accord
ing to
mount
ing circuit d
iagram.
5
6
7
8
1
2
3
4
Technical D
ata
Type of battery (C10; 1.8 V/Z; +20 °C)
12 V / 106 Ah
Rated voltage of all batteries
216 V
Number of all batteries
36 á 12 V
Battery dimensions in mm (W x H x D) 39.8 Ah
200 x 169 x 176
Battery dimensions in mm (W x H x D) 66.2 Ah
260.5 x 171 x 239
final pole
M-M6
Supply terminals
max. 35 mm²
W
eight incl. Batteries
1060 kg
Dimensions in mm (W x H x D)
2 x (800 x 2050 x 400)
Order no. of battery bloc 39.8 Ah
40066041395
Order no. of battery bloc 66.2 Ah
40066070902
Protection calss
IP 20
Wir
ing Set 4 0071 346 779 included
No.
Length
Number
5
300 mm
15
6
1000 mm
2
7
800 mm
1
8
2000 mm
1
Wir
ing Set 4 0071 346 778 included
No.
Length
Number
1
440 mm
13
2
800 mm
4
3
800 mm
1
4
2000 mm
1
1. Battery console
1. Battery console
1. Battery console
1. Battery console
2. Battery console
2. Battery console
2. Battery console
2. Battery console
3. Battery console
3. Battery console
3. Battery console
3. Battery console
4. Battery console
4. Battery console
5. Battery console
5. Battery console