39
Mounting and Operating Instructions CEAG Battery Cabinets
40071860035 (N) March 2016 www.ceag.de
3 Technical Data / Battery Installation
3. Battery console
3. Battery console
2. Battery console
2. Battery console
1. Battery console
1. Battery console
3.5.4 With battery set 50.4 Ah
For interconnection see chapter „Circuit Diagrams“
ZB-S/1
0C6
ZB-S/1
8C6
ZB-S/26C6*
EURO ZB.1/264K
EURO ZB.1/264K
*2250
1
2
3
4
5
Technical D
ata
Type of battery (C10; 1.8 V/Z; +20 °C)
12 V / 50.4 Ah
Rated voltage of all batteries
216 V
Number of all batteries
18 á 12 V
Battery dimensions in mm (L x W x H)
220 x 172 x 235
final pole
F-M6
Supply terminals
max. 35 mm²
W
eight incl. Batteries
505 kg
Dimensions in mm (W x H x D)
800 x 2050 x 600 (800x2250x600 for ZB-S/26C6)
Order no. batterie bloc
40066070917
Wir
ing Set 4 0071 347 449 included
No.
Length
Number
1
300 mm
12
2
360 mm
3
3
1000 mm
2
4
400 mm
1
5
1400 mm
1