3 Technical Data / Battery Installation
For interconnection see chapter „Circuit Diagrams“
3.1.10 Standard-Battery Cabinet 118 Ah
1
2
3
4
Technical D
ata
Type of battery (C10; 1.8 V/Z; +20 °C)
6 V / 118 Ah
Rated voltage of all batteries
216 V
Number of all batteries
36 á 6 V
Battery dimensions in mm (L x W x H)
272 x 166 x 190
final pole
M8
Supply terminals
max. 35 mm²
W
eight incl. Batteries
1200 kg
Dimensions in mm (W x H x D)
2 x (800 x 2050 x 400)
Order no. batterie bloc
40066070466
Protection calss
IP 20
Wir
ing Set 4 0071 346 775 included
No.
Length
Number
1
350 mm
26
2
800 mm
8
3
800 mm
2
4
2000 mm
2
1. Battery console
Right hinge
2. Battery console
3. Battery console
4. Battery console
5. Battery console