9
1.1.4. Arc sensors ARC-SP, ARC-SL and ARC-SM
Sensors placed in the switchgear transfer the light information to the I/O units.
Arc sensor ARC-SP
Figure: Arc sensor ARC-SP
•
Strong light is transformed to a current signal in the sensor
•
ARC-EP10/2.0 transfers the current signal to the master unit
•
Standard cable lengths 6 m and 20 m
•
The sensor type offers a cost-effective arc protection solution
•
Easy to install and replace
•
Normal installation involves one sensor in each switchgear compartment
•
Self-supervised arc sensor
Arc
fi bre sensor ARC-SL
Figure:
Arc
fi bre sensor ARC-SL
• The
fi bre sensor is a durable glass fi bre, which is manufactured in lengths of
10, 11, 12, 13, 15, 20 and 25 metres (the active sensor length is always 5m less)
•
The detected light information is transferred to the ARC-EL3/2.0 unit inside the fi bre
• The
fi bre will be installed to go through the supervised compartments
•
Monitoring the light information with a fi bre system is a cost-effective solution
e.g. in low voltage switchgears with several compartments
•
Self-supervised arc sensor
Содержание ARCON 2.0 Series
Страница 51: ...51 7 6 Block diagram 7 6 1 ARC EM 2 0 Figure Connections of ARC EM 2 0...
Страница 54: ...54 7 6 4 ARC EL3 2 0 7 6 5 ARC EC1 2 0...
Страница 64: ...64 9 Construction 9 1 Dimensional drawings 9 1 1 ARC EM 2 0 panel and semi flush mounting...
Страница 65: ...65 9 1 2 ARC EP10 2 2 0 din rail mounting...
Страница 66: ...9 1 3 ARC EP10 2 0 din rail mounting 66...
Страница 67: ...67 9 1 4 ARC EL3 2 0 din rail mounting...
Страница 68: ...68 9 1 5 ARC EC1 2 0 din rail mounting...
Страница 69: ...69 9 1 6 Fiber sensor mounting r min 50 mm...
Страница 70: ...70 9 1 7 Point sensor mounting...
Страница 82: ...82 10 Application examples 10 1 Applications 10 1 1 With a main busbar system...
Страница 83: ...83 10 1 2 With two main busbar systems...
Страница 84: ...84 10 1 3 With two main busbar systems and additional zone selection 4 zones...
Страница 85: ...85...