![Eaton ARCON 2.0 Series Скачать руководство пользователя страница 79](http://html1.mh-extra.com/html/eaton/arcon-2-0-series/arcon-2-0-series_operation-and-configuration-instructions-technical-description_3797414079.webp)
79
ARC-SL is an fi bre sensor that can be mounted on the switchgear to monitor several com-
partments simultaneously (various bus-bar compartmets, etc.).
The
fi bre must not touch any live parts of the switchgear or other hot components, since too
high temperatures may destroy the fi bre.
When mounting the sensor on the switchgear, ensure that the bending radius is long enough
(min. 50 mm) and that it is safe from the sharp edges of the switchgear.
NOTE! The sensor must not be exposed to direct sunlight or other strong light. Do not mount the
sensor directly under a light source.
NOTE! To avoid false tripping, cover any unused channels of the I/O unit.
ARC-SM
The portable pin sensor can be temporarily connected to the I/O units. It is used to improve
safety when working with live switchgear, for example, Attach the sensor close to the working
area, for example in the breast pocket of the maintenance man.
A pin sensor operates in the same way as a fi xed arc sensor. The only difference is free mo-
bility within the limits of the connecting cable.
Figure: Pin sensor ARC-SM
NOTE! To avoid faulty tripping, disconnect the pin sensor from the system immediately after use.
Содержание ARCON 2.0 Series
Страница 51: ...51 7 6 Block diagram 7 6 1 ARC EM 2 0 Figure Connections of ARC EM 2 0...
Страница 54: ...54 7 6 4 ARC EL3 2 0 7 6 5 ARC EC1 2 0...
Страница 64: ...64 9 Construction 9 1 Dimensional drawings 9 1 1 ARC EM 2 0 panel and semi flush mounting...
Страница 65: ...65 9 1 2 ARC EP10 2 2 0 din rail mounting...
Страница 66: ...9 1 3 ARC EP10 2 0 din rail mounting 66...
Страница 67: ...67 9 1 4 ARC EL3 2 0 din rail mounting...
Страница 68: ...68 9 1 5 ARC EC1 2 0 din rail mounting...
Страница 69: ...69 9 1 6 Fiber sensor mounting r min 50 mm...
Страница 70: ...70 9 1 7 Point sensor mounting...
Страница 82: ...82 10 Application examples 10 1 Applications 10 1 1 With a main busbar system...
Страница 83: ...83 10 1 2 With two main busbar systems...
Страница 84: ...84 10 1 3 With two main busbar systems and additional zone selection 4 zones...
Страница 85: ...85...