Access Power Solutions Installation Guide (APS6-400 Series)
92
Copyright © 2009-2010 Eaton Corporation. All Rights Reserved.
IPN 997-00012-53B December 2010
Test
Test procedure
Adjustment
Equalize
For details see Equalize test in System Controls on page
Fast Charge
For details see Fast Charge test in System Controls on page
Battery Test
For details see Battery Test in System Controls on page
In Discharge
Note 3
Connect load to the system.
Turn off the ac supply to the rectifiers.
Allow the battery to start discharging.
Ensure alarm operates.
Config Error
Note 4
Load incorrect configuration file.
- or -
Remove all rectifiers from the system.
Apply an incorrect external voltage to the system:
24V for a 48V system
48V for a 24V system
Ensure alarm operates.
User Assigned
Alarms
See User Digital Input test on page
Battery Current
Limit
For details see Battery Current Limit test in System
Controls on page
Rectifier No Load
Ensure the dc load and batteries are isolated from the
system.
Ensure alarm operates.
Rectifier Current
Limit
Apply a dc load to the system.
Turn off rectifiers until the remaining rectifiers reach the
Rectifier Current Limit
threshold.
- or -
Set the
Rectifier Current Limit
slightly below the existing
rectifier current being delivered to the load.
Ensure alarm operates.
High Rectifier
Temperature
Note 5
Unable to test.
AC Phase 1/2/3 Fail
Note 6
Turn off ac phase 1 to the power system.
Ensure alarm operates.
Repeat for phase 2 and phase 3.
AC Phase 1/2/3
Voltage
Note 6
Reduce the
High AC Threshold
below the existing ac
voltage.
Ensure alarm operates.
Increase the
Low AC Threshold
above the existing ac
voltage.
Ensure alarm operates.
AC Frequency
Note 6
Change the Nominal AC Frequency setting.
Change the AC Frequency Threshold.
Ensure alarm operates.
Engine Run Option
Note 7
Change the state of the digital input with
Engine Run
function.
Ensure alarm operates.