Access Power Solutions Installation Guide (APS6-400 Series)
26
Copyright © 2009-2010 Eaton Corporation. All Rights Reserved.
IPN 997-00012-53B December 2010
Step 2 - Terminate the cabling
Connect only voltage-free switch or relay contacts to Digital Inputs.
Do not exceed the voltage and current limits of the relay contacts.
For wire size and I/O ratings see Specifications on page
1
Route the cabling through the access hole in the Input/Output cover to the
terminal blocks on the I/O board.
2
Test the insulation and continuity of the cabling.
3
Terminate the wires into the push-connect terminals (see following diagram).
4
Replace the I/O board.
Input/Output (I/O) cover.
I/O board.
Digital input terminals (push-connect type).
Alarm relay (digital output) terminals (push-
connect type).
Step 3 - Replace the cover and secure cables
1
Replace the Input/Output (I/O) cover.
2
Use cable ties to secure the cable(s) and prevent strain on the connections.