10

Instructional Leaflet 

IB48041

Effective December 2009

Instructions for AMPGARD 400A

medium voltage starter

 

eaton corporatIon

 www.eaton.com

Figure 24. Unsnap Pin Collar

Figure 25. Remove Pin

Figure 26. Remove Three Line-Side and Three Load-Side Bolts  

(Bolt-In Contactor only) 

Isolation switch

The isolation switch consists of a fixed rear portion and a remov-

able front portion. The switch should operate smoothly in both 

directions, with an increase in resistance as the stabs engage the 

controller line fingers. Inspect for any signs of mechanical wear or 

overheating. 
To withdraw the removable portion:

1. 

Remove the three main fuses

2. 

Remove the control plug 

3. 

Remove the cotter pin and clevis pin from drive rod clevis

4. 

Remove the two bolts securing the removable portion of the 

switch to the fixed portion

5. 

Pull the switch forward, then down and out of the controller

 caution

take care not to let the switch quickly Drop Down as the 

removable portion separates from the fixeD portion or  

Damage to the shutter can occur.

Figure 27. Isolation Switch Control Plug

Figure 28. Isolation Switch Drive Rod

Line-Side 

Bolts (3)

Load-Side 

Bolts (3)

Collar

Control  

Plug

Disconnect 

by Removing 

Pin in Clevis

Drive Rod

Содержание Ampgard 400

Страница 1: ...former reduced voltage solid state or two speed type They may control induction or synchronous machines and they may be non reversing or reversing While this instructional leaflet is dedicated primari...

Страница 2: ...ake Break Short time current 30 seconds 1 second 8 6 milliseconds 0 5 cycle Standard service altitude Optional service altitude Mechanical life Electrical life BIL Dielectric strength 60 Hz Closing ti...

Страница 3: ...oor The low voltage compartment is fabricated from steel sheets to provide iso lation from the medium voltage components mounted behind the low voltage compartment A window is provided in the low volt...

Страница 4: ...y equipped with high interrupting contactors to prevent the inadvertent installation of standard interrupting contactors into those cells Figure 7 SL Vacuum Contactor Contactors are typically three po...

Страница 5: ...closing at the same time Low voltage control The low voltage control compartment is located in a steel pocket in the medium voltage door A low voltage door with up to four device panels provides acce...

Страница 6: ...ass ropes or cables through the lift holes Use slings with safety hooks or shackles of adequate load rating Each controller is properly adjusted at the factory before shipment However vibration and me...

Страница 7: ...Compartment Control connections Control wires may enter the enclosure from either the top or the bottom For lineups with main bus a low voltage wireway is located in the left front of the bus compartm...

Страница 8: ...are must be taken to ensure no damage is inflicted on the controller control power transformer CPT potential transformers PT or to the controller load Removal of the primary fuses is sufficient to pro...

Страница 9: ...of the fuse If a fuse has blown due to a fault it is likely that the other fuses experienced a similar overcurrent condition In this case Eaton recommends that all three fuses be replaced Ensure that...

Страница 10: ...e fingers Inspect for any signs of mechanical wear or overheating To withdraw the removable portion 1 Remove the three main fuses 2 Remove the control plug 3 Remove the cotter pin and clevis pin from...

Страница 11: ...Reinstallation is the reverse of the procedure previously discussed Make sure that the shaft of the removable portion of the switch is rotated to the fully open position before reinstallation Danger I...

Страница 12: ...ton Corporation All Rights Reserved Printed in USA Publication No IB48041 Z9119 December 2009 PowerChain Management is a registered trademark of Eaton Corporation All other trademarks are property of...

Отзывы: