background image

8

Instructional Leaflet 

IB48041

Effective December 2009

Instructions for AMPGARD 400A

medium voltage starter

 

eaton corporatIon

 www.eaton.com

Figure 18. Horizontal Wireway and Ground Bus 

Setting of adjustable protective devices

AMPGARD controllers may contain protective devices, such as 

solid-state motor protection relays, overcurrent relays, incomplete 

sequence timers, and other devices, critical to the proper operation 

of the starter. Due to the wide variation in job site parameters, these 

devices are not set at the factory. It is the purchaser’s responsibility 

to ensure that all adjustable devices are properly set before energiz-

ing the equipment. Warranty is void if adjustable devices are not 

properly set prior to initially starting the equipment.

 Danger

failure to properly set aDjustable Devices may result in  

equipment Damage, personal injury, or Death.

pre-startup checks

Before attempting to put a newly installed controller into service, 

study the wiring diagrams, control schematics, other order-specific 

drawings, and all instruction literature. Ensure that all adjustable 

devices, including protective relays and timers, have been  

properly set. 
Verify that the controller and motor are connected per the Eaton 

drawings. This is particularly essential in this class of equipment, as 

the fuse ratings, current transformers, and overload protection are 

based on the characteristics of the particular motor (or other load)  

to be controlled.
Ensure that all safety precautions have been taken and that the 

installation conforms to applicable regulations and safety practices.
The equipment should be free of dirt, scraps of wire, tools, and 

other foreign material.
The dielectric strength of the vacuum interrupters should be 

checked before the contactor is energized for the first time and  

regularly thereafter to detect at the earliest possible date any  

deterioration in the dielectric strength of the interrupter, because 

this may result in an interruption failure. The test is best performed  

with the contactor removed from the controller cubicle. Removal 

instructions can be found later in this instructional leaflet in the 

“Maintenance/Contactor” section. If testing is performed with the 

contactor installed, care must be taken to ensure no damage is 

inflicted on the controller control power transformer (CPT), potential 

transformers (PT), or to the controller load. Removal of the primary 

fuses is sufficient to protect the CPT or PTs. Cables to the load 

should be disconnected. Although an AC test is recommended, a 

DC test may be performed if only a DC test unit is available. A good 

vacuum interrupter will withstand a 16 kV–60 Hz test or a 23 kV–DC 

test across the normally open contact gap. When performing DC 

tests, the voltage should be raised in discrete steps until the final 

test voltage is reached. When tested with an AC high-potential  

tester, expect a capacitance leakage current of approximately  

1 milliampere per interrupter. Refer to IB-48018N for more  

information on dielectric testing of the vacuum interrupters.

The insulation level of the starter should be checked and recorded 

before the unit is energized.
Enclosure doors should close easily. Do not force doors closed, but 

rather look for improperly positioned contactors, isolating switches, 

or other devices.
Ensure that all phase barriers are in good condition and are properly 

installed. Note that larger and/or additional barriers are used when 

double-barrel fuses are in use. Refer to 

Figures 6

12

14

, and 

19

 

for examples.

 Danger

ensure that the correct barriers are useD with Double-barrel 

fuses. failure to install the correct phase barriers can result 

in equipment Damage, severe injury, or Death.

Figure 19. Lower Fuse Mounting with optional Fuse Clips

Verify that the contactor is fully inserted into the controller  

compartment. On stab-connected type contactors, verify that all  

finger-stab combinations are properly engaged. On bolt-connected 

contactors, verify that all connections have been properly torqued. 

On stab-connected contactors, a mounting bracket is provided to 

secure the contactor in the cell. Verify that the securing bolt is in 

place and is properly tightened to the bracket. A small gap between 

the contactor baseplate and the mounting bracket is normal. 

Figure 20. Contactor Hold-Down Bracket

 Danger

all sources of meDium voltage must be isolateD anD lockeD 

out at the upstream feeDer before the interlock check can be 

performeD. failure to isolate anD lock out all incoming power 

to the lineup can result in equipment Damage, severe injury,  

or Death.

Ground 

Bus

Horizontal 

Wireway 

(extends 

length of 

lineup)

Phase 

Barriers 

(4)

Hold-Down 

Bracket

Содержание Ampgard 400

Страница 1: ...former reduced voltage solid state or two speed type They may control induction or synchronous machines and they may be non reversing or reversing While this instructional leaflet is dedicated primari...

Страница 2: ...ake Break Short time current 30 seconds 1 second 8 6 milliseconds 0 5 cycle Standard service altitude Optional service altitude Mechanical life Electrical life BIL Dielectric strength 60 Hz Closing ti...

Страница 3: ...oor The low voltage compartment is fabricated from steel sheets to provide iso lation from the medium voltage components mounted behind the low voltage compartment A window is provided in the low volt...

Страница 4: ...y equipped with high interrupting contactors to prevent the inadvertent installation of standard interrupting contactors into those cells Figure 7 SL Vacuum Contactor Contactors are typically three po...

Страница 5: ...closing at the same time Low voltage control The low voltage control compartment is located in a steel pocket in the medium voltage door A low voltage door with up to four device panels provides acce...

Страница 6: ...ass ropes or cables through the lift holes Use slings with safety hooks or shackles of adequate load rating Each controller is properly adjusted at the factory before shipment However vibration and me...

Страница 7: ...Compartment Control connections Control wires may enter the enclosure from either the top or the bottom For lineups with main bus a low voltage wireway is located in the left front of the bus compartm...

Страница 8: ...are must be taken to ensure no damage is inflicted on the controller control power transformer CPT potential transformers PT or to the controller load Removal of the primary fuses is sufficient to pro...

Страница 9: ...of the fuse If a fuse has blown due to a fault it is likely that the other fuses experienced a similar overcurrent condition In this case Eaton recommends that all three fuses be replaced Ensure that...

Страница 10: ...e fingers Inspect for any signs of mechanical wear or overheating To withdraw the removable portion 1 Remove the three main fuses 2 Remove the control plug 3 Remove the cotter pin and clevis pin from...

Страница 11: ...Reinstallation is the reverse of the procedure previously discussed Make sure that the shaft of the removable portion of the switch is rotated to the fully open position before reinstallation Danger I...

Страница 12: ...ton Corporation All Rights Reserved Printed in USA Publication No IB48041 Z9119 December 2009 PowerChain Management is a registered trademark of Eaton Corporation All other trademarks are property of...

Отзывы: