background image

6

Instructional Leaflet 

IB48041

Effective December 2009

Instructions for AMPGARD 400A

medium voltage starter

 

eaton corporatIon

 www.eaton.com

Current transformers

A three-phase current transformer (CT) is provided as standard on all 

starters. The standard mounting location for the CT is under the con-

tactor load connection assembly. The three CTs in the assembly are 

provided with the proper ratio and output burden to work properly 

with the overload relay supplied in the control compartment.

Figure 12. Standard CT Mounting

Main bus

AMPGARD lineups are typically supplied with copper main bus. The 

bus is located in a 12-inch-high bus compartment mounted at the 

top of the lineup. Bus may be rated 1000, 1200, 2000, or 3000A. 

The standard bus is uninsulated and tin plated. Optional insulation 

and silver plating are available. Bus specifications can be found on 

the job-specific order drawings.

Figure 13. Main Bus Compartment, Top View

The main bus compartment in a starter section includes vertical  

bus drops to connect the starter(s) to the main bus. Also included 

are wireways for routing of motor load and control cables to the  

starters below.

Installation

Handling

An AMPGARD controller is insulated for high voltages and must be 

protected against damage during handling. The controller should 

remain in an upright position at all times.
Exercise extreme care during any movement and placement  

operations to prevent dropping or unintentional rolling or tipping. 

AMPGARD medium voltage equipment may be moved by forklift,  

rollers, or overhead crane.
A forklift is usually the most convenient method of handling the  

controller. Use safety straps around the protective packaging  

material when handling the controller with a forklift. Insert the forks 

under the shipping skid. Do not allow the end of the forks to enter 

the bottom of the enclosure.
Rod or pipe rollers provide a simple method for moving the  

controller on a level floor. The bottom of the AMPGARD structure is 

designed to be rolled without damage on minimum 2-inch diameter 

rollers, four rollers per 36-inch section.

AMPGARD controllers are shipped with two steel lifting angles,  

one in front and one in back, running the full width of the shipping 

section. Back-to-back units also have one in the back and one in the 

front, running the full width of the shipping section. Select or adjust 

the rigging lengths to compensate for any unequal distribution  

of the load, and maintain the controller in an upright position.  

Some controller interiors may contain heavy equipment, such as 

transformers, that can make the center of gravity vary considerably 

from the center of the lineup. 

Do not allow the angle between 

the lifting cables and vertical to exceed 45 degrees. 

Do not pass 

ropes or cables through the lift holes. Use slings with safety hooks 

or shackles of adequate load rating.

Each controller is properly adjusted at the factory before  

shipment. However, vibration and mechanical stresses imposed 

by transit and installation can adversely affect mechanical  

interlocks and other adjustments; therefore, a final inspection  

is essential before energizing. If this inspection reveals any  

portion of the controller has come out of adjustment, the  

controller should be readjusted according to information in  

this instruction book or by a qualified Eaton service engineer.

Storage

If it is necessary to store an AMPGARD controller before installation, 

keep it in a clean, dry location with ample air circulation and heat  

to prevent condensation. Like all electrical apparatus, an AMPGARD 

controller contains insulation that must be protected against dirt  

and moisture.

Mounting

AMPGARD controllers should be installed on a non-combustible 

level surface of sufficient strength to properly support the control-

ler’s mass. After the lineup has been placed in position, anchor bolts  

may be installed and tightened. Refer to the job-specific order  

drawings for the bolt locations. The use of half-inch diameter bolts  

is recommended.
Equipment located in certain seismic zones must be anchored to 

meet the requirements of those zones. Refer to Eaton I.B. 48042  

for instructions on mounting in these special locations. It is the 

user’s responsibility to ensure the mounting pad is sufficiently strong 

to properly anchor and support the equipment.
When an order includes two or more shipping sections, the order 

outline drawing will show the sequence in which the sections are 

to be lined up and which shipping splits are to be joined. A bus bar 

splice kit and a connecting hardware kit are supplied for each open 

joint between sections. 
Place the first shipping split into position. Move the second  

shipping split into position alongside the first, and use the six or  

eight 3/8 x 1.50-inch bolts and companion hardware to connect the 

two sideplates. Place one flat washer under the bolt head and one 

flat washer and one lock washer under the nut. Tighten each bolt to 

25 lb-ft (33 Nm).

Bus splicing

Connect the bus bars using the splice kit, including hardware  

(3/8-inch diameter) that is provided with the equipment. Tighten 

bolts to 25 lb-ft (33 Nm).

Power connections

Incoming power connects to the lineup in a variety of ways. Cables, 

bus from other close-coupled equipment, busduct, and transformer 

shunts are some of the more common methods. Note that these 

connections may be energized even when the starter isolation 

switch or other switching devices are in the open position. 

Ground 

Fault CT

High-

Interrupting 

Contactor  

Code Plate

Phase Barriers (4)

Three-Phase CT

Ground Bus

Main Bus 

(3000A 

shown)

Vertical 

Bus

Low Voltage 

Conduit 

Space

Upper Starter 

Medium 

Voltage 

Conduit Space
Lower Starter 

Medium 

Voltage 

Conduit Space

Содержание Ampgard 400

Страница 1: ...former reduced voltage solid state or two speed type They may control induction or synchronous machines and they may be non reversing or reversing While this instructional leaflet is dedicated primari...

Страница 2: ...ake Break Short time current 30 seconds 1 second 8 6 milliseconds 0 5 cycle Standard service altitude Optional service altitude Mechanical life Electrical life BIL Dielectric strength 60 Hz Closing ti...

Страница 3: ...oor The low voltage compartment is fabricated from steel sheets to provide iso lation from the medium voltage components mounted behind the low voltage compartment A window is provided in the low volt...

Страница 4: ...y equipped with high interrupting contactors to prevent the inadvertent installation of standard interrupting contactors into those cells Figure 7 SL Vacuum Contactor Contactors are typically three po...

Страница 5: ...closing at the same time Low voltage control The low voltage control compartment is located in a steel pocket in the medium voltage door A low voltage door with up to four device panels provides acce...

Страница 6: ...ass ropes or cables through the lift holes Use slings with safety hooks or shackles of adequate load rating Each controller is properly adjusted at the factory before shipment However vibration and me...

Страница 7: ...Compartment Control connections Control wires may enter the enclosure from either the top or the bottom For lineups with main bus a low voltage wireway is located in the left front of the bus compartm...

Страница 8: ...are must be taken to ensure no damage is inflicted on the controller control power transformer CPT potential transformers PT or to the controller load Removal of the primary fuses is sufficient to pro...

Страница 9: ...of the fuse If a fuse has blown due to a fault it is likely that the other fuses experienced a similar overcurrent condition In this case Eaton recommends that all three fuses be replaced Ensure that...

Страница 10: ...e fingers Inspect for any signs of mechanical wear or overheating To withdraw the removable portion 1 Remove the three main fuses 2 Remove the control plug 3 Remove the cotter pin and clevis pin from...

Страница 11: ...Reinstallation is the reverse of the procedure previously discussed Make sure that the shaft of the removable portion of the switch is rotated to the fully open position before reinstallation Danger I...

Страница 12: ...ton Corporation All Rights Reserved Printed in USA Publication No IB48041 Z9119 December 2009 PowerChain Management is a registered trademark of Eaton Corporation All other trademarks are property of...

Отзывы: