P-164000249
30-200 kW
33
Revision 2
User's and Installation Guide
Terminal function
Terminal
Function
Tightening torque Nm
AC input to UPS
rectifier
X1
L1, L2, L3, N
Check the tightening
torque from the con-
nector label.
AC input to bypass
X2
L1, L2, L3, N
Check the tightening
torque from the con-
nector label.
UPS output
X3
L1, L2, L3, N
Check the tightening
torque from the con-
nector label.
DC input from external
battery to UPS
X4
b, battery –
Check the tightening
torque from the con-
nector label.
Protective Earth
PE
PE
Check the tightening
torque from the con-
nector label.
Table 3-8: UPS power cable terminations
NOTE
External overcurrent protection is not provided by this product, but is required by codes. Refer
to Table 3-6: Minimum recommended multi-core cable and fuse sizes on page 31 for wiring
requirements. If an output lockable disconnect is required, it is to be supplied by the user.
CAUTION
To reduce the risk of fire, connect only to a circuit provided with maximum input circuit
breaker current ratings from Table 3-7: Rated and maximum currents for rated power and
voltage on page 31 in accordance with the national and local installation rules.
The line-to-line unbalanced output capability of the UPS is limited only by the full load per phase
current values for AC output to critical load shown in
Table 3-7: Rated and maximum currents for
rated power and voltage
on page 31. The recommended line-to-line load unbalance is 50 % or
less.
Source Protection for the AC Input to Bypass should suit the characteristics of the load and take
account of effects such as Inrush or Starting Current.
Bypass and output overcurrent protection and bypass and output disconnect switches are to be
provided by the user.
For UPS wiring diagrams, see
Chapter 2.1 Looking inside the UPS system
on page 9.
Содержание 93PM IBC-L
Страница 1: ...Eaton 93PM UPS P 164000249 30 200 kW User s and Installation Guide...
Страница 2: ......
Страница 3: ...Eaton 93PM UPS 30 200 kW User s and Installation Guide...
Страница 19: ...P 164000249 30 200 kW 11 Revision 2 User s and Installation Guide Figure 2 2 93PM 50 kW UPS wiring diagram...
Страница 50: ...42 30 200 kW P 164000249 User s and Installation Guide Revision 2 Figure 4 5 93PM battery cabinet EBC S...