6.4.2 Starting the UPS system in Bypass mode
If the inverter output of the UPS is not available and the critical load needs to be energized, perform
the following procedure:
CAUTION
In Bypass mode, the critical load is not protected from commercial power interruptions and
abnormalities.
1.
Unfasten the front door latch and swing the door open.
2.
Verify that rectifier input switches are closed if included inside the UPS system, and verify that
battery breaker is closed, and close the front door.
3.
Close the UPS input feeder circuit breaker.
4.
Close the UPS bypass input feeder circuit breaker.
5.
Observe the UPS control panel becoming active, indicating logic power.
Repeat steps 1-5 for each single UPS in the system.
6.
Press the
Controls
button in the main menu. The System Controls screen appears.
7.
On the System Controls screen, the system status should indicate SHUTDOWN.
8.
Press the
Go to bypass
button in the System Controls screen.
The critical load is immediately supplied by the bypass source, in Bypass mode.
9.
The UPS system is now operating in Bypass mode and the BYPASS status indicator is
illuminated.
6.4.3 Transfer from Double conversion mode to Bypass mode
To transfer the critical load to Bypass mode, perform the following procedure:
NOTE
In Bypass mode, the critical load is not protected from commercial power interruptions and
abnormalities.
1.
Press the
Controls
button in the main menu. The System controls screen appears.
2.
Press the
Go to bypass
button in the System Controls screen. The UPS system transfers to
Bypass mode and the critical load is immediately supplied by the bypass source. If the bypass
source is not available, the power processor remains on and an alarm sounds.
3.
The UPS system is now operating in Bypass mode and the BYPASS status indicator is
illuminated. The UPM status indicates READY. The system status indicates ON BYPASS.
DANGER
Power is present inside the UPS cabinets.
Содержание 93PM IBC-L
Страница 1: ...Eaton 93PM UPS P 164000249 30 200 kW User s and Installation Guide...
Страница 2: ......
Страница 3: ...Eaton 93PM UPS 30 200 kW User s and Installation Guide...
Страница 19: ...P 164000249 30 200 kW 11 Revision 2 User s and Installation Guide Figure 2 2 93PM 50 kW UPS wiring diagram...
Страница 50: ...42 30 200 kW P 164000249 User s and Installation Guide Revision 2 Figure 4 5 93PM battery cabinet EBC S...
Страница 51: ...P 164000249 30 200 kW 43 Revision 2 User s and Installation Guide Figure 4 6 93PM battery cabinet EBC L...