78
30-200 kW
P-164000249
User's and Installation Guide
Revision 2
Total voltage harmonic distortion
100 % linear load
100 % non-linear load
< 1 %
< 5 %
Rated output frequency
Output frequency variation
Slew rate
50 or 60 Hz, configurable
± 0,1 Hz
1 Hz/s
Overload capability at ambient 40 °C
(On inverter)
10 min 102-110 % load
60 sec 111-125 % load
10 sec 126-150 % load
300 ms > 150 % load
Overload capability at ambient 40 °C
(On inverter, stored energy mode)
10 min 102-110 % load
60 sec 111-125 % load
300 ms > 126 % load
Overload capability at ambient 40 °C
(On bypass)
Continuous < 125 % load
10 ms 1000 % load
Note! Bypass fuses may limit the overload capability.
Output current
See
Table 3-7: Rated and maximum currents for rated
power and voltage
on page 31
Load power factor, (Rated)
Load power factor, (Permitted range)
1.0
From 0.8 lagging to 0.8 leading
Table 8-3: UPS system output
8.4 Battery specification
Battery type
VRLA, 12 VCD
Содержание 93PM IBC-L
Страница 1: ...Eaton 93PM UPS P 164000249 30 200 kW User s and Installation Guide...
Страница 2: ......
Страница 3: ...Eaton 93PM UPS 30 200 kW User s and Installation Guide...
Страница 19: ...P 164000249 30 200 kW 11 Revision 2 User s and Installation Guide Figure 2 2 93PM 50 kW UPS wiring diagram...
Страница 50: ...42 30 200 kW P 164000249 User s and Installation Guide Revision 2 Figure 4 5 93PM battery cabinet EBC S...
Страница 51: ...P 164000249 30 200 kW 43 Revision 2 User s and Installation Guide Figure 4 6 93PM battery cabinet EBC L...