P-164000249
30-200 kW
77
Revision 2
User's and Installation Guide
8.2 UPS system input
Rated input voltage
Voltage tolerance, (Rectifier input)
Voltage tolerance, (Bypass input)
220/380 V; 230/400 V; 240/415 V
230 V -15 % / +20 %
230 V -15 % / +10 %
Rated input frequency
Frequency tolerance
50 or 60 Hz, user configurable
40 to 72 Hz
Number of input phases, (Rectifier input)
Number of input phases, (Bypass input)
3 N
3 N
Input power factor
0,99
Rated mains input current
Maximum mains input current
See
Table 3-7: Rated and maximum currents for
rated power and voltage
on page 31
Input current distortion at rated input current,
iTHD
30 kW: < 4,5 %
40-200 kW: < 3 %
Rectifier ramp-up, rectifier start and load step
10 A/s (default), configurable. Min 1A/s
Backfeed protection
Yes, for rectifier and bypass lines
Table 8-2: UPS system input
8.3 UPS system output
Number of output phases
3 N
Rated output voltage
220/380 V; 230/400 V; 240/415 V, configurable