Eaton 93PM Integrated Accessory Cabinet-Distribution (50–200 kW) Installation and Operation Manual P-164000229—Rev 09
3
–
A no distribution option provides a single 350A output breaker.
–
Neutral Current Monitoring available at the UPS display.
–
Optional factory pre-wiring to allow subfeed breakers to be field installed.
•
100 kW (208V/208V) features:
–
Optional 208/480 Vac input transformer provides conversion from 208 Vac facility power to feed the
93PM UPS 480 Vac input.
–
480/208 Vac output transformer provides 208 Vac output from the 480 Vac UPS output for
applications that require 208 Vac, and for use with the distribution panels suppling 208/120 Vac to the
critical load.
–
Can be used with a three-breaker Sidecar Integrated Accessory Cabinet-Bypass (SIAC-B) or wall
mount maintenance bypass.
–
One optional output distribution panel distributes the output power from the UPS to the load. The
distribution panel is behind the door on the front of the IAC-D. The 225A distribution panel with a 225A
main breaker can hold up to the equivalent of 42 single-pole branch circuit breakers (Cutler-Hammer
bolt-on type BAB or QBHW) that can be configured to meet facility needs.
–
Up to five optional 100-250A adjustable output distribution breakers are available to distribute the
output power from the UPS to larger critical loads. The breakers have adjustable trip rating and are
enclosed behind the hinged doors and trim panels on the front of the IAC-D.
–
A no distribution option provides a single 350A output breaker.
–
Neutral Current Monitoring available at the UPS display.
–
Optional factory pre-wiring to allow subfeed breakers to be field installed.
•
150 kW features:
–
480/208 Vac output transformer provides 208 Vac output from the 480 Vac UPS output for
applications that require 208 Vac, and for use with the distribution panels suppling 208/120 Vac to the
critical load.
–
Up to two optional output distribution panels distributes the output power from the UPS to the load.
The distribution panels are behind the door on the front of the IAC-D. Each 225A or 400A distribution
panel can hold up to 42 single-pole branch circuit breakers (either Cutler-Hammer bolt-on type BAB or
QBHW that can be configured to meet facility needs.
–
An optional single 225A distribution breaker for use with two panel board configurations.
–
Up to five optional 100-250A adjustable output distribution breakers are available to distribute the
output power from the UPS to larger critical loads. The breakers have adjustable trip rating and are
enclosed behind the hinged doors and trim panels on the front of the IAC-D.
–
A no distribution option provides a single 600A output breaker.
–
Optional Neutral Current Monitoring available at the UPS display.
–
Optional factory pre-wiring to allow subfeed breakers to be field installed
•
200 kW features:
–
480/208 Vac output transformer provides 208 Vac output from the 480 Vac UPS output for
applications that require 208 Vac, and for use with the distribution panels suppling 208/120 Vac to the
critical load.
–
Up to two optional output distribution panels distributes the output power from the UPS to the load.
The distribution panels are behind the door on the front of the IAC-D. Each 225A or 400A distribution