Eaton 93PM Integrated Accessory Cabinet-Distribution (50–200 kW) Installation and Operation Manual P-164000229—Rev 09
15
Table 2. IAC-D Cabinet Weights (Continued)
Model
Weight kg (lb)
Shipping
Installed
Point Loading
Eaton 93PM 150 kW IAC-D with output transformer
and two panelboards
955 (2106)
909 (2004)
4 at 227 (501)
Eaton 93PM 200 kW IAC-D with output transformer
and two panelboards
1023 (2256)
977 (2154)
4 at 244 (539)
Air inlets are in the bottom of the cabinet. Outlets are in the back of the cabinet for rear exhaust and in the top
of the cabinet for top exhaust.
Rear exhaust (see
):
•
50 kW: Natural convection air cooling regulates internal component temperature
•
100 kW: Natural convection air cooling regulates internal component temperature
•
100 kW 208/208: Forced air cooling only
•
150 kW: Forced air cooling only
•
200 kW: Forced air cooling only
Top exhaust (see
or
•
50 kW: Natural convection air cooling
•
100 kW: Forced air cooling only
•
100 kW 208/208: Forced air cooling only
•
150 kW: Forced air cooling only
•
200 kW: Forced air cooling only
Allow clearance on top or in back of the cabinet depending on type of exhaust for proper air circulation. The
clearances required around the IAC-D cabinet are shown in
.