Eaton 93PM Integrated Accessory Cabinet-Distribution (50–200 kW) Installation and Operation Manual P-164000229—Rev 09
53
Figure 28. Output Breaker Output Power Terminal Detail – 50 kW and 100 kW
AC Output to
Critical Load
Phase A (XOB-2)
Phase C (XOB-6)
Phase B (XOB-4)
44..33..44
TTw
woo--H
Hoollee B
Baarrrreell LLuugg TTeerrm
miinnaattiioonnss ttoo B
Buuss B
Baarr IInnssttaallllaattiioonn
Paragraph
150 kW and 200 kW Output Wiring
requires connecting the output breaker power wiring using
2-hole barrel lugs (see
for recommended lugs). See
for the hardware sequence when
installing the lugs to the bus bars. Tighten the bolt to the torque value listed in
Proceed to paragraph
150 kW and 200 kW Output Wiring
.
NOTE
Conical washers are special purpose washers that look similar to flat washers, except
for a slight conical shape. When installing conical washers, the top of the dome should
be next to the bolt head and the base of the washer should be against a flat surface such
as a bus bar, flat washer, or large terminal.