3.4.5
Maintenance bypass switch
The optional internal maintenance bypass switch (MBS) for 100-120 kVA units
consists of input and bypass input switches, an output switch and a
maintenance bypass switch. The input and bypass input switches are used to
control the AC input to the UPS. The output switch is used to control the inverter
output. The MBS enables partial isolation of the UPS so that a limited number of
components can be serviced without interrupting power critical systems.
3.4.6
24 V Battery shunt trip (OVT)
93E units are able to trip external battery breakers through 24 VDC OVT control.
3.5 Battery system
The battery system is in an external cabinet. The battery system provides
emergency short-term backup power to safeguard operation during brownouts,
blackouts, and other power interruptions. The battery system is equipped with
lead-acid batteries.
3.6 Basic system configurations
The following basic UPS system configurations are possible:
• Single UPS with 1-4 external battery cabinets
• Single UPS with external batteries and accessory cabinets
The UPS system configuration can be enhanced by adding optional accessories
such as a remote emergency power-off (remote EPO) control, or MiniSlot
communication cards.
3.7 Single UPS unit system oneline configurations
The system oneline drawings provided in this section show the simplified
internal structure of the UPS, battery supply, and basic maintenance bypass.
Table 3: Oneline configurations
Oneline drawing
UPS model
Input voltage
Output voltage
System type
93E G2 100/100
93E G2 120/120
93E G2 200/160
93E G2 200/200
380/400/415 VAC 380/400/415 VAC Single reverse trans-
fer UPS with external
battery
Eaton 93E Generation 2 UPS 100-200 kVA
(380/400/415V)
User's and installation guide
©
Eaton Corporation plc 2019. All rights reserved.
Revision: 002
Document ID: P-164000848
28 (118)