Units
Rating 50/60 Hz
Input and output
voltage
Volts
400/400
400/400
400/400
400/400
AC input to UPS
rectifier (0.99 Mini-
mum pF)
Full load current
plus battery re-
charge current (3)
Phases, (1) Neutral,
(1) Ground
A
150
180
240
300
Conductor size (L1,
L2, L3 and N)
min.
mm
2
35
50
70
95
max.
mm
2
95
120
150
240
AC input to UPS by-
pass (Five Wire, Du-
al-Feed)
Full load current
(3) Phases, (1) Neu-
tral
A
144
173
231
289
Conductor size (L1,
L2, L3 and N)
min.
mm
2
35
50
95
185
max.
mm
2
95
120
240
240
DC input from exter-
nal battery (1) Posi-
tive, (1) Negative
A
206
247
330
412
Conductor size
min.
mm
2
50
70
185
300
max.
mm
2
120
150
400
400
AC output to critical
load (Five Wire)
Full load current
(3) Phases, (1) Neu-
tral
A
144
173
231
289
Conductor size (L1,
L2, L3 and N)
min.
mm
2
35
35
50
70
max.
mm
2
95
95
150
150
Grounding:
- Conductor size
(PE)
min.
mm
2
35
50
70
95
max.
mm
2
95
120
150
240
Neutral (N)
(Mains/Load: Non-
linear lad)
1.7 times
Backfeed protection
device
Clearance distance: ≥ 2.0 mm
Break time ≤ 15 s