52
8-10 kVA, 50/60 Hz (1-phase input) &
8-15 kVA, 50/60 Hz (3-phase input)
P-164000341
User's Guide
Revision 1
Description
Available settings
Default setting
XSlot input signal (long break via
Rx)
Nothing
XSlot shutdown signal activation
delay before the signal is accept-
ed.
Step: 1 sec.
5 sec.
Bypass and synchronisation:
Usage of bypass
[Enabled], [Disabled]
Enabled
Require synch at transfer on by-
pass
[Required], [Not Required]
Not required
Transfer on bypass on overload
[Immediately], [after delay]
Immediately
Synchronization enable
[Enabled], [Disabled]
Enabled
Bypass voltage deviation high limit
+1% ... +20%, step: 1%
+10%
Bypass voltage deviation low limit
-1% ... -20%, step: 1%
-15%
Synchronization window
0.5 ... 3.0 Hz, step: 0.1 Hz
±2.0 Hz
Frequency slew rate (not in paral-
lel mode)
0.1 ... 3.0 Hz/s, step 0.1 Hz/s
0.2 Hz/s
Battery information and settings:
ABM charging cycling disable
[Enabled], [Disabled]
Enabled
Charging temp compensation
[Enabled], [Disabled]
Enabled
Battery size setting
Step: 1 Watts/cell
24 Watts/cell
Number of 36 pcs. battery strings
0 (no batteries), 1, 2, 3, 4...
1 string
Battery low alarm level
Step: 0.01 V/cell
1.88 V/cell
Automatic battery support test
[Enabled], [Disabled]
Enabled
Maximum charging current
Step: 0.1 A [max. 25 Amps]
3 A
Output on, automatic delay time
before turning the output on
[Disabled], [Set delay, step: 1 sec]
0 sec.
Output off, automatic delay time
on battery after which output is
turned off
[Disabled], [Set delay, step: 1 sec]
Disabled
User preferences: