P-164000341
8-10 kVA, 50/60 Hz (1-phase input) &
8-15 kVA, 50/60 Hz (3-phase input)
53
Revision 1
User's Guide
Description
Available settings
Default setting
Operation priority while rectifier in-
put break
[On battery], [On bypass]
On battery
Site wiring fault w/ wrong Neutral
connection
[Enabled], [Disabled]
Disabled
Power Strategy
[Standard], [High Efficiency]
Standard
Parallel settings:
Parallel unit number
[Single unit], [Unit #1], [Unit #2],
[Unit #3], [Unit #4]
Single unit
Parallel operation mode
[Redundant mode], [Capacity mode]
Redundant mode
Synchronization
[Enabled], [Disabled]
Enabled
Start auto calibration
Parallel XCP
[System], [Unit]
System
Minimum units to support load
[0], [1], [2], [3], [4]
2
Table 8-2: User setting in the LCD menu screen
8.2.1 Configuring user settings
User settings can be configured via front panel. Select Settings from main menu and then select User
Settings.
8.2.2 Changing language
Pressing and holding down the first button on the left for about 3 seconds selects the language
menu. This action is possible from any LCD menu screen.
The default firmware has four main languages: English, Spanish, French and German. Other local
language packages including Chinese, Greek and Russian can be requested from the local service
representative.
8.2.3 Changing charging current
Maximum charging current setting should be checked when needed back-up time needs more than 3
Amps charging current.
Load (kVA) p.f. 0.7
Back-up time
Min current
Load (kVA) p.f. 0.7
Back-up time
Min current
10
1 h
1.8 A
15
1 h
2.5 A
10
3 h
4 A
15
3 h
6.5 A
Содержание 9155 N