 thermostats are configured to operate in different modes via the configuration parameters

 

accessible through the maintenance mode.

 

To enter the maintenance mode click the COG WHEEL icon in the FURTHER SETTINGS SCREEN

 

and enter the maintenance mode password (default 6666).

 

Note: 

The maintenance mode password can be changed in the configuration settings. Make sure that

 

you note the new password if changed. If the Maintenance Code is set as 0000, the Maintenance

 

Code entry screen is bypassed (i.e. no protection).

 

CONTROL SETTINGS

 

Parameter Name

 

Description

 

Range

 

Nominal Setpoint

 

Nominal Setpoint

 

 

0.0...95.0 °F (Default 70.0°F)

 

ECO Heating Setpoint

 

ECO Mode Heating Setpoint

 

0.0...95.0 °F (Default 60.0°F)

 

ECO Cooling Setpoint

 

ECO Mode Cooling Setpoint

 

0.0...95.0 °F (Default 82.0°F)

 

Frost Setpoint

 

Night Frost Setpoint (OFF Mode)

 

0.0...95.0 °F (Default 46.0°F)

 

Min Setpoint Adj

 

Minimum Adjustable Setpoint

 

0.0...95.0 °F (Default 57.0 °F)

 

Max Setpoint Adj

 

Maximum Adjustable Setpoint

 

0.0...95.0 °F (Default 86.0 °F)

 

Hysteresis

 

Temperature Control Hysteresis

 

0.0..20.0 °F (Default 1.8°F)

 

Control Type

 

Heating and/or Cooling Control (change-over via

 

0 = Heating Control (default)

 

Digital input or over the communications network)

 

1 = Cooling Control

 

2 = Heating/Cooling Change-Over

 

Min Limit

 

Underfloor Heating Minimum Limit Setpoint

 

0.0...95.0 °F (Default 64.0°F)

 

Max Limit

 

Underfloor Heating Maximum Limit Setpoint

 

0.0...122.0 °F (Default 86.0°F)

 

Limit Hysteresis

 

Underfloor Heating Control Hysteresis

 

0.0..10.0 (default 1.8)

 

INPUTS

 

Parameter Name

 

Description

 

Range

 

RI1 Mode

 

Remote Temperature Sensor RI1 Mode

 

0 = Disabled (Default)

 

(status monitoring over the network is active for all

 

1 = Control

 

active modes)

 

2 = Outside Temperature (Display)

 

3 = Network (Networked Solutions)

 

RI2 Mode

 

Remote Temperature Sensor RI1 Mode

 

0 = Disabled (Default)

 

 

(status monitoring over the network is active for all

 

1 = Underfloor Min-Max Control

 

active modes)

 

2 = Outside Sensor (Display)

 

3 = Network (networked Solutions)

 

Digital Input Mode

 

Digital Input Operation

 

(status monitoring over the network is active for all

 

modes)

 

0 = Disabled (no 

EIO

 effect)

 

= Close for ECO

 

2 = Open for ECO

 

2 = Close for OFF/FROST

 

3 = Open for OFF/FROST

 

4 = Heating / Cooling Mode

 

5 = DI Contact Alarm

 

 

6 = Network

 

Digital Input Delay

 

Digital Input Delay Timer (transition from active to

 

0..7200 seconds (Default 0s)

 

non-active)

 

Outside Temp Source

 

Source for the Outside Temperature Display

 

0 = Built-In Sensor

 

1 = Network Sensor

 

Internal Sensor Cal

 

Internal Sensor One Point Compensation

 

-10.0..+10.0 °F

RI1 Cal

 

Sensor Connected to RI1 Calibration

 

-10.0..+10.0 °F

RI2 Cal

 

Sensor Connected to RI2 Calibration

 

-10.0..+10.0 °F

Humidity Cal

 

Humidity Calibration

 

-10.0..+10.0 % rH

Содержание EIO-55 Series

Страница 1: ...EIO 55 PRODUCT MANUAL BACnet or Modbus Touchscreen Thermostat EIO 55 MOD EIO 55 BAC EIO 55 MOD HUM EIO 55 BAC HUM...

Страница 2: ...Model Type Model Description Modbus 3 5 Touchscreen Thermostat Non Programmable 24Vac dc Power Supply Non UL BACnet MSTP 3 5 Touchscreen Thermostat Non Programmable 24Vac dc Power Supply Non UL EIO 55...

Страница 3: ...000 6 1 2001 Generic Immunity EN60730 1 2016 Low Voltage EN6100 4 2 4 5 11 ESD Transient Surges Interruptions Degree of Protection IP20 Housing Housing Material Polycarbonate Plastics Self Extinguishi...

Страница 4: ...FUNCTION BASED ICON in holiday mode shows the holiday icon from where the holiday mode can be cancelled in cleaning mode shows the cleaning icon from where the mode can be can celled in BOOST mode sho...

Страница 5: ...fault the built in temperature sensor but can be configured to use an external sensor connected to RI1 The description for the room temperature can be changed via Room Text parameter in the configurat...

Страница 6: ...s the thermostat state i e if the thermostat has been switched to ECO mode via a digital input or over the network the user can cancel the mode through the touchscreen OFF Mode The thermostats can be...

Страница 7: ...ivated The lock mode can be configured to work in different ways DISABLED Lock Mode Icon Not Available ON OFF BOOST ONLY Allows On Off Boost Buttons Only ADJUST ONLY Allows Temperature Adjustment Or O...

Страница 8: ...ct closes the DI Contact Alarm alarm message is displayed on the screen Network option is selected when the digital input is used for monitoring purposes only Humidity Measurement and Display RH optio...

Страница 9: ...ol 2 Heating Cooling Change Over Min Limit Underfloor Heating Minimum Limit Setpoint 0 0 95 0 F Default 64 0 F Max Limit Underfloor Heating Maximum Limit Setpoint 0 0 122 0 F Default 86 0 F Limit Hyst...

Страница 10: ...C Enable AC Icon Network Variable 0 Disabled default 1 Enabled Enable Holiday Enable Holiday Icon 0 Disabled 1 Enabled default Humidity Display Enable Disable Humidity Display if option fitted 0 Disab...

Страница 11: ...nges are carried out over the network Modbus or BACnet then NonVol Update register object is required to be forced on to save the changes The register will automatically return to normal state when us...

Страница 12: ...Default 64 0 F Register Parameter Description Data Type Raw Data Range 104 Minimum Setpoint Unsigned 16 0 950 0 0 95 0 F Default 57 0 F 105 Maximum Setpoint Unsigned 16 0 950 0 0 95 0 F Default 86 0...

Страница 13: ...2 Override Lights Unsigned 16 0 2 0 None default 1 Override On 2 Override Off 133 Override Lock Mode Unsigned 16 0 2 0 None default 1 Lock Screen 2 Cancel Lock Mode Register Parameter Description Data...

Страница 14: ...trol 0 1 Off On Relay Output Override Relay Mode Network FUNCTION CODE 04 READ INPUT REGISTERS 0 Built In Temperature Measurement Signed 16 400 3020 40 0 150 0 C 40 0 302 0 F 1 Underfloor Temperature...

Страница 15: ...AV 9 LCD Brightness AV 10 Control Hysteresis AV 11 Network Temp AV 12 Nominal Setpoint Binary Input 3 BI 0 Digital Input DI1 BI 1 Cleaning Mode Status BI 2 Boost Mode Status Binary Output 9 BO 0 Relay...

Страница 16: ...ture Sensor Unsigned 0 Disabled Default Mode 1 Main Control 2 Outdoor Temperature Display 3 System Networked Solutions 40108 Rin2 Underfloor Temperature Unsigned 0 Disabled default Sensor Mode 1 Min M...

Страница 17: ...d 1 Room Default Description 2 Floor 3 Outside 4 Zone 1 5 Zone 2 6 Zone 3 7 Bathroom 8 Sauna 9 Bedroom 10 Kitchen 11 Cooler 12 Flow 13 Hot Water 14 Tank 15 Pool 40140 Zone 2 Text Floor Sensor Unsigned...

Отзывы: