NOTE: Application Configuration Object exposes the configuration parameters over the
BACnet. However please check if your BACnet client can support Proprietary Object types to
be able to access these parameters. Alternatively set the configuration parameters through
the
EIO
touchscreen.
Property Name /ID
Attributes
Range
Default
Required
Object Identifier
R
proprietary-128
Object
Object Name
R/W
"App_Config"
Properties
Object Type
R
proprietary-128
Optional
None
Properties
Property ID
Description
BACnet Data Type
Range
Proprietary
30106
Alarm State
Unsigned
0 = No Fault
Properties
1
= Internal sensor fault
2
= RI1 fault
3
= Internal sensor & RI fault
4
= RI2 fault
5
= Internal Sensor & RI2 fault
6
= RI1 & RI2 fault
7
= Internal sensor, RI1 & RI2 Fault
40101
ECO Heating Setpoint
REAL
0.0...95.0 °F (Default 60.0°F)
40102
ECO Cooling Setpoint
REAL
0.0...95.0 °F (Default 82.0°F)
40103
Frost Setpoint
REAL
0.0...95.0 °F (Default 46.0°F)
40104
Minimum Setpoint
REAL
0.0...95.0 °F (Default 57.0 °F)
40105
Maximum Setpoint
REAL
0.0...95.0 °F (Default 86.0 °F)
40106
Hysteresis
REAL
0.0..20.0 °F (Default 1.8°F)
40107
Rin1 Remote Temperature Sensor
Unsigned
0 = Disabled (Default)
Mode
1
= Main Control
2
= Outdoor Temperature (Display)
3
= System (Networked Solutions)
40108
Rin2 Underfloor Temperature
Unsigned
0 = Disabled (default)
Sensor Mode
1
= Min-Max Control
2
= Outdoor Sensor
3
= System (Networked Solutions)
40109
Control Type
Unsigned
0 = Heating Control (default)
1
= Cooling Control
2
= Heating/Cooling Change-Over
40110
Min Floor Temp Limit
REAL
0.0...95.0°F (Default 64.0°F)
40111
Max Floor Temp Limit
REAL
0.0...122.0°F (Default 86.0°F)
40012
Floor Hysteresis
REAL
0.0..10.0 (default 1.8)
40113
Digital Input Mode
Unsigned
0 = Disabled
1
= Close for ECO (Default)
2
= Open for ECO
3
= Close for OFF/FROST
4
= Open for OFF/FROST
5
= Heating / Cooling Mode
6
= Digital Input Alarm
7
= Network
40114
Digital Input Delay
Unsigned
0..7200 seconds (Default 0s)
40115
Enable Lights Symbol
Unsigned
0 = Disabled (default)
1
= Enabled
40116
Enable AC Symbol
Unsigned
0 = Disabled (default)
1
= Enabled
40117
Power Up
Unsigned
0 = Thermostat On when power applied
(default)
1
= Thermostat Off when power applied
40118
Lock Mode
Unsigned
1 = Lock mode disabled (default)
2
= On/Off/Boost workable only
3
= Temp settings only available
4
= All buttons disabled (no input)
40119
Temperature Unit Swap Icon
Unsigned
0 = Disabled
1
= Enabled (default)
40121
RI1 Sensor Calibration
REAL
-10.0..+10.0 °F
40122
RI2 Sensor Calibration
REAL
-10.0..+10.0 °F