App_Config Object

 

NOTE: Application Configuration Object exposes the configuration parameters over the

 

BACnet. However please check if your BACnet client can support Proprietary Object types to

 

be able to access these parameters. Alternatively set the configuration parameters through

 

the 

EIO

 touchscreen.

 

Property Name /ID

  

Attributes

 

Range

 

Default

 

Required

 

Object Identifier

 

R

 

proprietary-128

 

Object

 

Object Name

 

R/W

 

"App_Config"

 

Properties

 

Object Type

 

R

 

proprietary-128

 

Optional

 

None

 

Properties

 

Property ID

 

Description

 

BACnet Data Type

 

Range

 

Proprietary

 

30106

 

Alarm State

 

Unsigned

 

0 = No Fault

 

Properties

 

1

 

= Internal sensor fault

 

2

 

= RI1 fault

 

3

 

= Internal sensor & RI fault

 

4

 

= RI2 fault

 

5

 

= Internal Sensor & RI2 fault

 

6

 

= RI1 & RI2 fault

 

7

 

= Internal sensor, RI1 & RI2 Fault

 

40101

 

ECO Heating Setpoint

 

REAL

 

0.0...95.0 °F (Default 60.0°F)

 

40102

 

ECO Cooling Setpoint

 

REAL

 

0.0...95.0 °F (Default 82.0°F)

 

40103

 

Frost Setpoint

 

REAL

 

0.0...95.0 °F (Default 46.0°F)

 

40104

 

Minimum Setpoint

 

REAL

 

0.0...95.0 °F (Default 57.0 °F)

 

40105

 

Maximum Setpoint

 

REAL

 

0.0...95.0 °F (Default 86.0 °F)

 

40106

 

Hysteresis

 

REAL

 

0.0..20.0 °F (Default 1.8°F)

 

40107

 

Rin1 Remote Temperature Sensor

 

Unsigned

 

0 = Disabled (Default)

 

Mode

 

1

 

= Main Control

 

2

 

= Outdoor Temperature (Display)

 

3

 

= System (Networked Solutions)

 

40108

 

Rin2 Underfloor Temperature

 

Unsigned

 

0 = Disabled (default)

 

Sensor Mode

 

1

 

= Min-Max Control

 

2

 

= Outdoor Sensor

 

3

 

= System (Networked Solutions)

 

40109

 

Control Type

 

Unsigned

 

0 = Heating Control (default)

 

1

 

= Cooling Control

 

2

 

= Heating/Cooling Change-Over

 

40110

 

Min Floor Temp Limit

 

REAL

 

0.0...95.0°F (Default 64.0°F)

 

40111

 

Max Floor Temp Limit

 

REAL

 

0.0...122.0°F (Default 86.0°F)

 

40012

 

Floor Hysteresis

 

REAL

 

0.0..10.0 (default 1.8)

 

40113

 

Digital Input Mode

 

Unsigned

 

0 = Disabled

 

1

 

= Close for ECO (Default)

 

2

 

= Open for ECO

 

3

 

= Close for OFF/FROST

 

4

 

= Open for OFF/FROST

 

5

 

= Heating / Cooling Mode

 

6

 

= Digital Input Alarm

 

7

 

= Network

 

40114

 

Digital Input Delay

 

Unsigned

 

0..7200 seconds (Default 0s)

 

40115

 

Enable Lights Symbol

 

Unsigned

 

0 = Disabled (default)

 

1

 

= Enabled

 

40116

 

Enable AC Symbol

 

Unsigned

 

0 = Disabled (default)

 

1

 

= Enabled

 

40117

 

Power Up

 

Unsigned

 

0 = Thermostat On when power applied

 

(default)

 

1

 

= Thermostat Off when power applied

 

40118

 

Lock Mode

 

Unsigned

 

1 = Lock mode disabled (default)

 

2

 

= On/Off/Boost workable only

 

3

 

= Temp settings only available

 

4

 

= All buttons disabled (no input)

 

40119

 

Temperature Unit Swap Icon

 

Unsigned

 

0 = Disabled

 

1

 

= Enabled (default)

 

40121

 

RI1 Sensor Calibration

 

REAL

 

-10.0..+10.0 °F

40122

 

RI2 Sensor Calibration

 

REAL

 

-10.0..+10.0 °F

Содержание EIO-55 Series

Страница 1: ...EIO 55 PRODUCT MANUAL BACnet or Modbus Touchscreen Thermostat EIO 55 MOD EIO 55 BAC EIO 55 MOD HUM EIO 55 BAC HUM...

Страница 2: ...Model Type Model Description Modbus 3 5 Touchscreen Thermostat Non Programmable 24Vac dc Power Supply Non UL BACnet MSTP 3 5 Touchscreen Thermostat Non Programmable 24Vac dc Power Supply Non UL EIO 55...

Страница 3: ...000 6 1 2001 Generic Immunity EN60730 1 2016 Low Voltage EN6100 4 2 4 5 11 ESD Transient Surges Interruptions Degree of Protection IP20 Housing Housing Material Polycarbonate Plastics Self Extinguishi...

Страница 4: ...FUNCTION BASED ICON in holiday mode shows the holiday icon from where the holiday mode can be cancelled in cleaning mode shows the cleaning icon from where the mode can be can celled in BOOST mode sho...

Страница 5: ...fault the built in temperature sensor but can be configured to use an external sensor connected to RI1 The description for the room temperature can be changed via Room Text parameter in the configurat...

Страница 6: ...s the thermostat state i e if the thermostat has been switched to ECO mode via a digital input or over the network the user can cancel the mode through the touchscreen OFF Mode The thermostats can be...

Страница 7: ...ivated The lock mode can be configured to work in different ways DISABLED Lock Mode Icon Not Available ON OFF BOOST ONLY Allows On Off Boost Buttons Only ADJUST ONLY Allows Temperature Adjustment Or O...

Страница 8: ...ct closes the DI Contact Alarm alarm message is displayed on the screen Network option is selected when the digital input is used for monitoring purposes only Humidity Measurement and Display RH optio...

Страница 9: ...ol 2 Heating Cooling Change Over Min Limit Underfloor Heating Minimum Limit Setpoint 0 0 95 0 F Default 64 0 F Max Limit Underfloor Heating Maximum Limit Setpoint 0 0 122 0 F Default 86 0 F Limit Hyst...

Страница 10: ...C Enable AC Icon Network Variable 0 Disabled default 1 Enabled Enable Holiday Enable Holiday Icon 0 Disabled 1 Enabled default Humidity Display Enable Disable Humidity Display if option fitted 0 Disab...

Страница 11: ...nges are carried out over the network Modbus or BACnet then NonVol Update register object is required to be forced on to save the changes The register will automatically return to normal state when us...

Страница 12: ...Default 64 0 F Register Parameter Description Data Type Raw Data Range 104 Minimum Setpoint Unsigned 16 0 950 0 0 95 0 F Default 57 0 F 105 Maximum Setpoint Unsigned 16 0 950 0 0 95 0 F Default 86 0...

Страница 13: ...2 Override Lights Unsigned 16 0 2 0 None default 1 Override On 2 Override Off 133 Override Lock Mode Unsigned 16 0 2 0 None default 1 Lock Screen 2 Cancel Lock Mode Register Parameter Description Data...

Страница 14: ...trol 0 1 Off On Relay Output Override Relay Mode Network FUNCTION CODE 04 READ INPUT REGISTERS 0 Built In Temperature Measurement Signed 16 400 3020 40 0 150 0 C 40 0 302 0 F 1 Underfloor Temperature...

Страница 15: ...AV 9 LCD Brightness AV 10 Control Hysteresis AV 11 Network Temp AV 12 Nominal Setpoint Binary Input 3 BI 0 Digital Input DI1 BI 1 Cleaning Mode Status BI 2 Boost Mode Status Binary Output 9 BO 0 Relay...

Страница 16: ...ture Sensor Unsigned 0 Disabled Default Mode 1 Main Control 2 Outdoor Temperature Display 3 System Networked Solutions 40108 Rin2 Underfloor Temperature Unsigned 0 Disabled default Sensor Mode 1 Min M...

Страница 17: ...d 1 Room Default Description 2 Floor 3 Outside 4 Zone 1 5 Zone 2 6 Zone 3 7 Bathroom 8 Sauna 9 Bedroom 10 Kitchen 11 Cooler 12 Flow 13 Hot Water 14 Tank 15 Pool 40140 Zone 2 Text Floor Sensor Unsigned...

Отзывы: