EasyIO EIO-55 Series Скачать руководство пользователя страница 5

EIO

-55 

  4 

LOCK icon is used to lock the thermostat. Number of different lock modes options exist.

HOLIDAY icon is used to switch the thermostat to holiday mode (ECO setpoint or Off Mode)

CLEANING icon is used to enable timed cleaning mode.

COG WHEEL icon allows entry to the maintenance mode.

The FURTHER SETTINGS screen is protected by the Staff Code. As default the Staff Code is disabled (0000). If activated, the user will 
need to enter the 

Staff Code

 to enter the screen.

 

Temperature Displays

 

Room

70

°F

 

.1

EIO

 thermostats show the measured temperatures inside the SMALL ACTION CIRCLE. The

 

enabled temperatu

 

res rotate in and out in a sequence.

 

Room temperature is always displayed on the ACTION CIRCLE. The room 
temperature uses as default the built-in temperature sensor but can be configured 
to use an external sensor connected to RI1. The description for the room 
temperature can be changed via 

Room Text

 parameter in the configuration 

pages.

Floor

68

°F

 

.7

Outside

62

°F

 

.6

 

Floor Temperature is displayed on the ACTION CIRCLE if the MIN- MAX 
operation has been selected for the RI2 input (underfloor minimum/maximum 
control). The description for the floor temperature can be changed via 

Floor Text

 

parameter in the configuration pages.

 

Outside Temperature is displayed on the ACTION CIRCLE if RI1/RI2 has been 
selected or if the 

Outside Temp Source

 parameter has been set to Network and 

valid network value is sent to the thermostat. The description for the outside 
temperature can be changed via 

Outside Text

 parameter in the configuration 

pages. By changing the description the outside temperature display can be used 
to indicate many other types of measurements.

 

Содержание EIO-55 Series

Страница 1: ...EIO 55 PRODUCT MANUAL BACnet or Modbus Touchscreen Thermostat EIO 55 MOD EIO 55 BAC EIO 55 MOD HUM EIO 55 BAC HUM...

Страница 2: ...Model Type Model Description Modbus 3 5 Touchscreen Thermostat Non Programmable 24Vac dc Power Supply Non UL BACnet MSTP 3 5 Touchscreen Thermostat Non Programmable 24Vac dc Power Supply Non UL EIO 55...

Страница 3: ...000 6 1 2001 Generic Immunity EN60730 1 2016 Low Voltage EN6100 4 2 4 5 11 ESD Transient Surges Interruptions Degree of Protection IP20 Housing Housing Material Polycarbonate Plastics Self Extinguishi...

Страница 4: ...FUNCTION BASED ICON in holiday mode shows the holiday icon from where the holiday mode can be cancelled in cleaning mode shows the cleaning icon from where the mode can be can celled in BOOST mode sho...

Страница 5: ...fault the built in temperature sensor but can be configured to use an external sensor connected to RI1 The description for the room temperature can be changed via Room Text parameter in the configurat...

Страница 6: ...s the thermostat state i e if the thermostat has been switched to ECO mode via a digital input or over the network the user can cancel the mode through the touchscreen OFF Mode The thermostats can be...

Страница 7: ...ivated The lock mode can be configured to work in different ways DISABLED Lock Mode Icon Not Available ON OFF BOOST ONLY Allows On Off Boost Buttons Only ADJUST ONLY Allows Temperature Adjustment Or O...

Страница 8: ...ct closes the DI Contact Alarm alarm message is displayed on the screen Network option is selected when the digital input is used for monitoring purposes only Humidity Measurement and Display RH optio...

Страница 9: ...ol 2 Heating Cooling Change Over Min Limit Underfloor Heating Minimum Limit Setpoint 0 0 95 0 F Default 64 0 F Max Limit Underfloor Heating Maximum Limit Setpoint 0 0 122 0 F Default 86 0 F Limit Hyst...

Страница 10: ...C Enable AC Icon Network Variable 0 Disabled default 1 Enabled Enable Holiday Enable Holiday Icon 0 Disabled 1 Enabled default Humidity Display Enable Disable Humidity Display if option fitted 0 Disab...

Страница 11: ...nges are carried out over the network Modbus or BACnet then NonVol Update register object is required to be forced on to save the changes The register will automatically return to normal state when us...

Страница 12: ...Default 64 0 F Register Parameter Description Data Type Raw Data Range 104 Minimum Setpoint Unsigned 16 0 950 0 0 95 0 F Default 57 0 F 105 Maximum Setpoint Unsigned 16 0 950 0 0 95 0 F Default 86 0...

Страница 13: ...2 Override Lights Unsigned 16 0 2 0 None default 1 Override On 2 Override Off 133 Override Lock Mode Unsigned 16 0 2 0 None default 1 Lock Screen 2 Cancel Lock Mode Register Parameter Description Data...

Страница 14: ...trol 0 1 Off On Relay Output Override Relay Mode Network FUNCTION CODE 04 READ INPUT REGISTERS 0 Built In Temperature Measurement Signed 16 400 3020 40 0 150 0 C 40 0 302 0 F 1 Underfloor Temperature...

Страница 15: ...AV 9 LCD Brightness AV 10 Control Hysteresis AV 11 Network Temp AV 12 Nominal Setpoint Binary Input 3 BI 0 Digital Input DI1 BI 1 Cleaning Mode Status BI 2 Boost Mode Status Binary Output 9 BO 0 Relay...

Страница 16: ...ture Sensor Unsigned 0 Disabled Default Mode 1 Main Control 2 Outdoor Temperature Display 3 System Networked Solutions 40108 Rin2 Underfloor Temperature Unsigned 0 Disabled default Sensor Mode 1 Min M...

Страница 17: ...d 1 Room Default Description 2 Floor 3 Outside 4 Zone 1 5 Zone 2 6 Zone 3 7 Bathroom 8 Sauna 9 Bedroom 10 Kitchen 11 Cooler 12 Flow 13 Hot Water 14 Tank 15 Pool 40140 Zone 2 Text Floor Sensor Unsigned...

Отзывы: