Typical Thermostat Home

 

 

Screens

 

The images below illustrate the typical home screens on the 

EIO

 thermostats. The screen is touch

 

sensitive and shows the current status of the thermostat. Inside the red/blue/white ring the thermostat 
shows the current target temperature. The intensity of the red/blue ring changes based on the 

temperature differing from the target temperature.

 

The small circle indicates the current room temperature (and if enabled the floor temperature and/or 

outside temperature, and/or relative humidity via a smooth transition effect).

 

In the Cleaning Mode the number inside the large circle indicates the remaining cleaning time. The 

Boost icon changes to Cleaning icon and by pressing it the cleaning mode can be cancelled..

 

In the Holiday Mode the home screen shows the current ECO mode target temperature, and ECO 

icon. By pressing the Holiday Mode Icon, the holiday can be cancelled anytime. 

Touchscreen

 

The 

EIO

 room thermostat home screen has multiple touch sensitive areas that allow the thermostat

 

settings to be changed.

 

UP and DOWN arrows; to alter the current target temperature temporarily.

SMALL ACTION CIRCLE (that contains current room temperature etc.); allows access to FUR-

 

 

 

THER SETTINGS AND INFORMATION screen.

 

FUNCTION BASED ICON; in holiday mode shows the holiday icon from where the holiday mode
can be cancelled, in cleaning mode shows the cleaning icon from where the mode can be can-

 

 

 

celled; in BOOST mode shows the BOOST icon from where the output can be Boosted on; in

 

OFF mode shows the OFF icon where the OFF mode can be cancelled.

 

ECO icon; when ECO mode is on, the ECO mode can be cancelled from the button.

A/C ICON; when AC is enabled the AC can be enabled/disabled from this icon (systems only).

LIGHTS ICON; when LIGHTS are enabled, the lights can be enabled/disabled from this icon
(systems only)

UNIT ICON; the user can change between °C and °F for display

Touchscreen Backlight

 

Further Settings and

 

Information

 

The touchscreen backlight level can be adjusted through the maintenance mode. During the normal

 

operation after 30 seconds of inactivity, the touchscreen dims to the "stand-by" level set. If the

 

backlight level is set to 0, the screen backlight switches off.

 

By pressing the DIM icon when the screen is active the screen is immediately dimmed to the

 

"stand-by" level. Pressing the DIM icon when the device is in the "stand-by level", switches the

 

backlight OFF.

 

The screen backlight is automatically activated when it is touched.

 

NOTE: To enter FURTHER SETTINGS screen, press SMALL ACTION CIRCLE (temperature

 

display) on the home screen.

 

The FURTHER SETTINGS shows additional user settings options on the 

EIO

 thermostats:-

 

OFF icon to switch thermostat to OFF

Содержание EIO-55 Series

Страница 1: ...EIO 55 PRODUCT MANUAL BACnet or Modbus Touchscreen Thermostat EIO 55 MOD EIO 55 BAC EIO 55 MOD HUM EIO 55 BAC HUM...

Страница 2: ...Model Type Model Description Modbus 3 5 Touchscreen Thermostat Non Programmable 24Vac dc Power Supply Non UL BACnet MSTP 3 5 Touchscreen Thermostat Non Programmable 24Vac dc Power Supply Non UL EIO 55...

Страница 3: ...000 6 1 2001 Generic Immunity EN60730 1 2016 Low Voltage EN6100 4 2 4 5 11 ESD Transient Surges Interruptions Degree of Protection IP20 Housing Housing Material Polycarbonate Plastics Self Extinguishi...

Страница 4: ...FUNCTION BASED ICON in holiday mode shows the holiday icon from where the holiday mode can be cancelled in cleaning mode shows the cleaning icon from where the mode can be can celled in BOOST mode sho...

Страница 5: ...fault the built in temperature sensor but can be configured to use an external sensor connected to RI1 The description for the room temperature can be changed via Room Text parameter in the configurat...

Страница 6: ...s the thermostat state i e if the thermostat has been switched to ECO mode via a digital input or over the network the user can cancel the mode through the touchscreen OFF Mode The thermostats can be...

Страница 7: ...ivated The lock mode can be configured to work in different ways DISABLED Lock Mode Icon Not Available ON OFF BOOST ONLY Allows On Off Boost Buttons Only ADJUST ONLY Allows Temperature Adjustment Or O...

Страница 8: ...ct closes the DI Contact Alarm alarm message is displayed on the screen Network option is selected when the digital input is used for monitoring purposes only Humidity Measurement and Display RH optio...

Страница 9: ...ol 2 Heating Cooling Change Over Min Limit Underfloor Heating Minimum Limit Setpoint 0 0 95 0 F Default 64 0 F Max Limit Underfloor Heating Maximum Limit Setpoint 0 0 122 0 F Default 86 0 F Limit Hyst...

Страница 10: ...C Enable AC Icon Network Variable 0 Disabled default 1 Enabled Enable Holiday Enable Holiday Icon 0 Disabled 1 Enabled default Humidity Display Enable Disable Humidity Display if option fitted 0 Disab...

Страница 11: ...nges are carried out over the network Modbus or BACnet then NonVol Update register object is required to be forced on to save the changes The register will automatically return to normal state when us...

Страница 12: ...Default 64 0 F Register Parameter Description Data Type Raw Data Range 104 Minimum Setpoint Unsigned 16 0 950 0 0 95 0 F Default 57 0 F 105 Maximum Setpoint Unsigned 16 0 950 0 0 95 0 F Default 86 0...

Страница 13: ...2 Override Lights Unsigned 16 0 2 0 None default 1 Override On 2 Override Off 133 Override Lock Mode Unsigned 16 0 2 0 None default 1 Lock Screen 2 Cancel Lock Mode Register Parameter Description Data...

Страница 14: ...trol 0 1 Off On Relay Output Override Relay Mode Network FUNCTION CODE 04 READ INPUT REGISTERS 0 Built In Temperature Measurement Signed 16 400 3020 40 0 150 0 C 40 0 302 0 F 1 Underfloor Temperature...

Страница 15: ...AV 9 LCD Brightness AV 10 Control Hysteresis AV 11 Network Temp AV 12 Nominal Setpoint Binary Input 3 BI 0 Digital Input DI1 BI 1 Cleaning Mode Status BI 2 Boost Mode Status Binary Output 9 BO 0 Relay...

Страница 16: ...ture Sensor Unsigned 0 Disabled Default Mode 1 Main Control 2 Outdoor Temperature Display 3 System Networked Solutions 40108 Rin2 Underfloor Temperature Unsigned 0 Disabled default Sensor Mode 1 Min M...

Страница 17: ...d 1 Room Default Description 2 Floor 3 Outside 4 Zone 1 5 Zone 2 6 Zone 3 7 Bathroom 8 Sauna 9 Bedroom 10 Kitchen 11 Cooler 12 Flow 13 Hot Water 14 Tank 15 Pool 40140 Zone 2 Text Floor Sensor Unsigned...

Отзывы: