EasyIO EIO-55 Series Скачать руководство пользователя страница 14

EIO

-55 

  13 

11 = Cooler

 

12 = Flow

 

13 = Hot Water

 

14 = Tank

 

15 = Pool

 

142

 

Outside Temperature Source

 

Unsigned 16

 

0..1

 

0 = Buillt-In Sensor (Default)

 

1

 

= Network Sensor

 

143

 

Outside Air Temperature - Network Write

 

Signed 16

 

-580...1220

-58.0...122.0 °F (Default 0.0)

300

 

Modbus Address

 

Unsigned 16

 

0..247

 

0..247

 

(Default 1)

 

301

 

Modbus Baud Rate

 

Unsigned 16

 

0..4

 

0

 

= 9600 (Default)

 

1

 

= 19200

 

2

 

= 38400

 

3

 

= 57600

 

4

 

= 76800

 

302

 

Modbus Parity

 

Unsigned 16

 

0..2

 

0

 

= None (Default)

 

1

 

= Odd

 

2

 

= Even

 

303

 

Stop Bits

 

Unsigned 16

 

0...1

 

0

 

= 1 Stop Bit (Default)

 

1

 

= 2 Stop Bits

 

400

 

Force Reset

 

Unsigned 16

 

0..1

 

0

 

= Normal

 

1

 

= Force Reset

 

401

 

Non Volatile Memory Update

 

Unsigned 16

 

0..1

 

0

 

= Normal

 

1

 

= Update

 

403

 

Force Factory Defaults

 

Unsigned 16

 

0..1

 

0

 

= Normal

 

1

 

= Force Factory Defaults

 

Legacy Modbus Registers

 

The below Modbus registers are duplicate registers for legacy product support.

 

Register

 

Parameter Description

 

Data Type

 

Raw Data

 

Range

 

FUNCTION CODE 01 - READ COILS

 

FUNCTION CODE 05 - WRITE SINGLE COIL

 

3

 

Relay Output (Read Only, Relay Mode=Control)

 

0..1

 

Off - On

 

Relay Output Override (Relay Mode=Network)

 

FUNCTION CODE 04 - READ INPUT REGISTERS

 

0

 

Built-In Temperature Measurement

 

Signed 16

 

-400...3020

-40.0...150.0°C
(-40.0..302.0°F)

1

 

Underfloor Temperature Measurement

 

Signed 16

 

-400...3020

-40.0...150.0°C

(Resistive Input 2)

 

 

(-40.0..302.0°F)

FUNCTION CODE 03 - READ HOLDING REGISTERS

 

FUNCTION CODE 06 - WRITE SINGLE HOLDING REGISTER

 

FUNCTION CODE 16 - WRITE MULTIPLE HOLDING REGISTERS

 

1

 

Unit Status. Reports Day/ECO status. Can be

 

Unsigned 16

 

0..1

 

0 = Day

 

used to override to ECO. Reset locally.

 

1 = Night ECO Mode

 

2

 

Nominal Setpoint

 

Unsigned 16

 

0...950

 

0.0...95.0 °F (Default 70°F)

 

14

 

Minimum Setpoint

 

Unsigned 16

 

0...950

 

0.0...95.0°F (Default 57°F)

 

15

 

Maximum Setpoint

 

Unsigned 16

 

0...950

 

0.0...95.0°F (Default 86°F)

 

16

 

Hysteresis

 

Unsigned 16

 

0..200

 

0.0..20.0°F (Default 1.8°F)

 

18

 

Frost Setpoint

 

Unsigned 16

 

0...950

 

0.0...95.0°F (Default 46°F)

 

19

 

Modbus Address

 

Unsigned 16

 

0..247

 

0..247 (Default 1)

 

BACnet Interoperability

 

Building Blocks Supported

 

(Annex K)

 

Application Service

 

Initiate

 

Execute

 

BIBB

 

ReadProperty

 

Yes

 

DS-RP-B

 

ReadPropertyMultiple

 

Yes

 

DS-RPM-B

 

WriteProperty

 

Yes

 

DS-WP-B

 

ReinitializeDevice

 

Yes

 

Who-Is

 

Yes

 

DM-DDB-B

 

I-Am

Yes

 

Who-Has

 

Yes

 

DM-DOB-B

 

I-Have

Yes

 

Содержание EIO-55 Series

Страница 1: ...EIO 55 PRODUCT MANUAL BACnet or Modbus Touchscreen Thermostat EIO 55 MOD EIO 55 BAC EIO 55 MOD HUM EIO 55 BAC HUM...

Страница 2: ...Model Type Model Description Modbus 3 5 Touchscreen Thermostat Non Programmable 24Vac dc Power Supply Non UL BACnet MSTP 3 5 Touchscreen Thermostat Non Programmable 24Vac dc Power Supply Non UL EIO 55...

Страница 3: ...000 6 1 2001 Generic Immunity EN60730 1 2016 Low Voltage EN6100 4 2 4 5 11 ESD Transient Surges Interruptions Degree of Protection IP20 Housing Housing Material Polycarbonate Plastics Self Extinguishi...

Страница 4: ...FUNCTION BASED ICON in holiday mode shows the holiday icon from where the holiday mode can be cancelled in cleaning mode shows the cleaning icon from where the mode can be can celled in BOOST mode sho...

Страница 5: ...fault the built in temperature sensor but can be configured to use an external sensor connected to RI1 The description for the room temperature can be changed via Room Text parameter in the configurat...

Страница 6: ...s the thermostat state i e if the thermostat has been switched to ECO mode via a digital input or over the network the user can cancel the mode through the touchscreen OFF Mode The thermostats can be...

Страница 7: ...ivated The lock mode can be configured to work in different ways DISABLED Lock Mode Icon Not Available ON OFF BOOST ONLY Allows On Off Boost Buttons Only ADJUST ONLY Allows Temperature Adjustment Or O...

Страница 8: ...ct closes the DI Contact Alarm alarm message is displayed on the screen Network option is selected when the digital input is used for monitoring purposes only Humidity Measurement and Display RH optio...

Страница 9: ...ol 2 Heating Cooling Change Over Min Limit Underfloor Heating Minimum Limit Setpoint 0 0 95 0 F Default 64 0 F Max Limit Underfloor Heating Maximum Limit Setpoint 0 0 122 0 F Default 86 0 F Limit Hyst...

Страница 10: ...C Enable AC Icon Network Variable 0 Disabled default 1 Enabled Enable Holiday Enable Holiday Icon 0 Disabled 1 Enabled default Humidity Display Enable Disable Humidity Display if option fitted 0 Disab...

Страница 11: ...nges are carried out over the network Modbus or BACnet then NonVol Update register object is required to be forced on to save the changes The register will automatically return to normal state when us...

Страница 12: ...Default 64 0 F Register Parameter Description Data Type Raw Data Range 104 Minimum Setpoint Unsigned 16 0 950 0 0 95 0 F Default 57 0 F 105 Maximum Setpoint Unsigned 16 0 950 0 0 95 0 F Default 86 0...

Страница 13: ...2 Override Lights Unsigned 16 0 2 0 None default 1 Override On 2 Override Off 133 Override Lock Mode Unsigned 16 0 2 0 None default 1 Lock Screen 2 Cancel Lock Mode Register Parameter Description Data...

Страница 14: ...trol 0 1 Off On Relay Output Override Relay Mode Network FUNCTION CODE 04 READ INPUT REGISTERS 0 Built In Temperature Measurement Signed 16 400 3020 40 0 150 0 C 40 0 302 0 F 1 Underfloor Temperature...

Страница 15: ...AV 9 LCD Brightness AV 10 Control Hysteresis AV 11 Network Temp AV 12 Nominal Setpoint Binary Input 3 BI 0 Digital Input DI1 BI 1 Cleaning Mode Status BI 2 Boost Mode Status Binary Output 9 BO 0 Relay...

Страница 16: ...ture Sensor Unsigned 0 Disabled Default Mode 1 Main Control 2 Outdoor Temperature Display 3 System Networked Solutions 40108 Rin2 Underfloor Temperature Unsigned 0 Disabled default Sensor Mode 1 Min M...

Страница 17: ...d 1 Room Default Description 2 Floor 3 Outside 4 Zone 1 5 Zone 2 6 Zone 3 7 Bathroom 8 Sauna 9 Bedroom 10 Kitchen 11 Cooler 12 Flow 13 Hot Water 14 Tank 15 Pool 40140 Zone 2 Text Floor Sensor Unsigned...

Отзывы: