EIO
-55
10
SYSTEM
Parameter Name
Description
Range
Address
Modbus Address (Only Modbus versions)
0..247 (Default 1)
BACnet MAC Address (Only BACnet versions)
0..127 (Default 1)
Baud Rate (Only Modbus/BACnet versions)
Modbus / BACnet Baud Rate
0
= 9600 (Default)
1
= 19200
2
= 38400
3
= 57600
4
= 76800
Parity (Only Modbus/BACnet versions)
Parity
0
= None (Default)
1
= Odd
2
= Even
Stop Bits (Only Modbus/BACnet versions)
Stop Bits
0
= 1 Stop Bit (Default)
1
= 2 Stop Bits
Device ID (Only BACnet versions)
BACnet Device ID
0..4,194,303
(Default Auto=651001)
Service Pin (Only BACnet versions)
Bacnet Service Pin (when activated the device
0
= Disabled (default)
sends BACnet I-AM message)
1
= Enabled
Maintenance Code
Maintenance Mode Password
0000 - 9999 (default 6666)
Staff Code
Staff Page Password - Access Password to Further
0000 - 9999 (default 0000 =
Settings Screen
disabled)
Language
Default Language for User Screens
0
= English (Default)
1
= Finnish
2
= Swedish
Reload Default
Reload Factory Default Settings
0
= Off (default)
1
= On
Version
Software Version
x.xx (Modbus/BACnet)
NOTE: If the communication settings have been changed, they are activated upon exiting the Maintenance Mode - the device
carries out a soft reset. Alternatively, power cycle will activate the new communication settings
Parameter Storage
The configuration parameters are stored in the non-volatile memory. When the changes are carried out via the display, the parameters
are stored in the non- volatile memory when the controller returns to a normal display mode. If the changes are carried out over the
network (Modbus or BACnet), then "NonVol Update" register/object is required to be forced on to save the changes. The register will
automatically return to normal state when using Modbus. In BACnet the object needs to re-triggered.
Modbus Registers
The controller supports the following Modbus registers and function codes. The default communication speed is 9600 bps, 8 data bits,
Parity None and 1 Stop Bit. The default Modbus Slave address is 1. The device Parity can be changed between Odd, None and Even.
The baud rate is selectable between 9600, 19200, 38400, 57600 and 76800 bps. The table shows the register offsets starting from 0 (0
Base) register address. For example, the Temperature is read from Modbus register 100 using Function Code 04. Some Modbus
masters will require one to be added to Modbus registers (i.e. 1 Base). In this case Function Code 04, register 101 needs to be entered.
Register
Parameter Description
Data Type
Raw Data
Range
FUNCTION CODE 01 - READ COILS
FUNCTION CODE 05 - WRITE SINGLE COIL
FUNCTION CODE 15 - WRITE MULTIPLE COILS
100
Off Mode Override
0..1
Off - On
101
ECO Mode Override
0..1
Off - On
102
Heating/Cooling Mode (change-over mode)
0..1
0 = Heating, 1 = Cooling
FUNCTION CODE 02 - READ DISCRETE INPUTS
100
Digital Input Status
0..1
Off - On
101
Relay Output Status
0..1
Off - On
102
Holiday Mode Status
0..1
Off - On
103
Light Switch Status
0..1
Off - On
104
A/C Switch Status
0..1
Off - On
105
Cleaning Mode Status
0..1
Off - On
106
Screen Lock Status
0..1
Off - On
107
Boost Status
0..1
Off - On
108
ECO Mode Status
0..1
Off - On
109
Frost Status
0..1
Off - On
FUNCTION CODE 04 - READ INPUT REGISTERS
100
Built-In Temperature Measurement
Signed 16
-400...3020
-40.0...150.0°C