EasyIO EIO-55 Series Скачать руководство пользователя страница 11

EIO

-55 

  10 

SYSTEM

 

Parameter Name

 

Description

 

Range

 

Address

 

Modbus Address (Only Modbus versions)

 

0..247 (Default 1)

 

BACnet MAC Address (Only BACnet versions)

 

0..127 (Default 1)

 

Baud Rate (Only Modbus/BACnet versions)

 

Modbus / BACnet Baud Rate

 

0

 

= 9600 (Default)

 

1

 

= 19200

 

2

 

= 38400

 

3

 

= 57600

 

4

 

= 76800

 

Parity (Only Modbus/BACnet versions)

 

Parity

 

0

 

= None (Default)

 

1

 

= Odd

 

2

 

= Even

 

Stop Bits (Only Modbus/BACnet versions)

 

Stop Bits

 

0

 

= 1 Stop Bit (Default)

 

1

 

= 2 Stop Bits

 

Device ID (Only BACnet versions)

 

BACnet Device ID

 

0..4,194,303

 

(Default Auto=651001)

 

Service Pin (Only BACnet versions)

 

Bacnet Service Pin (when activated the device

 

0

 

= Disabled (default)

 

sends BACnet I-AM message)

 

1

 

= Enabled

 

Maintenance Code

 

Maintenance Mode Password

 

0000 - 9999 (default 6666)

 

Staff Code

 

Staff Page Password - Access Password to Further

 

0000 - 9999 (default 0000 =

 

Settings Screen

 

disabled)

 

Language

 

Default Language for User Screens

 

0

 

= English (Default)

 

1

 

= Finnish

 

2

 

= Swedish

 

Reload Default

 

Reload Factory Default Settings

 

0

 

= Off (default)

 

1

 

= On

 

Version

 

Software Version

 

x.xx (Modbus/BACnet)

NOTE: If the communication settings have been changed, they are activated upon exiting the Maintenance Mode - the device 

carries out a soft reset. Alternatively, power cycle will activate the new communication settings 

Parameter Storage 

The configuration parameters are stored in the non-volatile memory. When the changes are carried out via the display, the parameters 
are stored in the non- volatile memory when the controller returns to a normal display mode. If the changes are carried out over the 
network (Modbus or BACnet), then "NonVol Update" register/object is required to be forced on to save the changes. The register will 
automatically return to normal state when using Modbus. In BACnet the object needs to re-triggered.

  

Modbus Registers 

The controller supports the following Modbus registers and function codes. The default communication speed is 9600 bps, 8 data bits, 
Parity None and 1 Stop Bit. The default Modbus Slave address is 1. The device Parity can be changed between Odd, None and Even. 
The baud rate is selectable between 9600, 19200, 38400, 57600 and 76800 bps. The table shows the register offsets starting from 0 (0 
Base) register address. For example, the Temperature is read from Modbus register 100 using Function Code 04. Some Modbus 
masters will require one to be added to Modbus registers (i.e. 1 Base). In this case Function Code 04, register 101 needs to be entered. 

Register

 

Parameter Description

 

Data Type

 

Raw Data

 

Range

 

FUNCTION CODE 01 - READ COILS

 

FUNCTION CODE 05 - WRITE SINGLE COIL

 

 

FUNCTION CODE 15 - WRITE MULTIPLE COILS

 

100

 

Off Mode Override

 

0..1

 

Off - On

 

101

 

ECO Mode Override

 

0..1

 

Off - On

 

102

 

Heating/Cooling Mode (change-over mode)

 

0..1

 

0 = Heating, 1 = Cooling

 

FUNCTION CODE 02 - READ DISCRETE INPUTS

 

100

 

Digital Input Status

 

0..1

 

Off - On

 

101

 

Relay Output Status

 

0..1

 

Off - On

 

102

 

Holiday Mode Status

 

0..1

 

Off - On

 

103

 

Light Switch Status

 

0..1

 

Off - On

 

104

 

A/C Switch Status

 

0..1

 

Off - On

 

105

 

Cleaning Mode Status

 

0..1

 

Off - On

 

106

 

Screen Lock Status

 

0..1

 

Off - On

 

107

 

Boost Status

 

0..1

 

Off - On

 

108

 

ECO Mode Status

 

0..1

 

Off - On

 

109

 

Frost Status

 

0..1

 

Off - On

 

FUNCTION CODE 04 - READ INPUT REGISTERS

 

100

 

Built-In Temperature Measurement

 

Signed 16

 

-400...3020

-40.0...150.0°C

Содержание EIO-55 Series

Страница 1: ...EIO 55 PRODUCT MANUAL BACnet or Modbus Touchscreen Thermostat EIO 55 MOD EIO 55 BAC EIO 55 MOD HUM EIO 55 BAC HUM...

Страница 2: ...Model Type Model Description Modbus 3 5 Touchscreen Thermostat Non Programmable 24Vac dc Power Supply Non UL BACnet MSTP 3 5 Touchscreen Thermostat Non Programmable 24Vac dc Power Supply Non UL EIO 55...

Страница 3: ...000 6 1 2001 Generic Immunity EN60730 1 2016 Low Voltage EN6100 4 2 4 5 11 ESD Transient Surges Interruptions Degree of Protection IP20 Housing Housing Material Polycarbonate Plastics Self Extinguishi...

Страница 4: ...FUNCTION BASED ICON in holiday mode shows the holiday icon from where the holiday mode can be cancelled in cleaning mode shows the cleaning icon from where the mode can be can celled in BOOST mode sho...

Страница 5: ...fault the built in temperature sensor but can be configured to use an external sensor connected to RI1 The description for the room temperature can be changed via Room Text parameter in the configurat...

Страница 6: ...s the thermostat state i e if the thermostat has been switched to ECO mode via a digital input or over the network the user can cancel the mode through the touchscreen OFF Mode The thermostats can be...

Страница 7: ...ivated The lock mode can be configured to work in different ways DISABLED Lock Mode Icon Not Available ON OFF BOOST ONLY Allows On Off Boost Buttons Only ADJUST ONLY Allows Temperature Adjustment Or O...

Страница 8: ...ct closes the DI Contact Alarm alarm message is displayed on the screen Network option is selected when the digital input is used for monitoring purposes only Humidity Measurement and Display RH optio...

Страница 9: ...ol 2 Heating Cooling Change Over Min Limit Underfloor Heating Minimum Limit Setpoint 0 0 95 0 F Default 64 0 F Max Limit Underfloor Heating Maximum Limit Setpoint 0 0 122 0 F Default 86 0 F Limit Hyst...

Страница 10: ...C Enable AC Icon Network Variable 0 Disabled default 1 Enabled Enable Holiday Enable Holiday Icon 0 Disabled 1 Enabled default Humidity Display Enable Disable Humidity Display if option fitted 0 Disab...

Страница 11: ...nges are carried out over the network Modbus or BACnet then NonVol Update register object is required to be forced on to save the changes The register will automatically return to normal state when us...

Страница 12: ...Default 64 0 F Register Parameter Description Data Type Raw Data Range 104 Minimum Setpoint Unsigned 16 0 950 0 0 95 0 F Default 57 0 F 105 Maximum Setpoint Unsigned 16 0 950 0 0 95 0 F Default 86 0...

Страница 13: ...2 Override Lights Unsigned 16 0 2 0 None default 1 Override On 2 Override Off 133 Override Lock Mode Unsigned 16 0 2 0 None default 1 Lock Screen 2 Cancel Lock Mode Register Parameter Description Data...

Страница 14: ...trol 0 1 Off On Relay Output Override Relay Mode Network FUNCTION CODE 04 READ INPUT REGISTERS 0 Built In Temperature Measurement Signed 16 400 3020 40 0 150 0 C 40 0 302 0 F 1 Underfloor Temperature...

Страница 15: ...AV 9 LCD Brightness AV 10 Control Hysteresis AV 11 Network Temp AV 12 Nominal Setpoint Binary Input 3 BI 0 Digital Input DI1 BI 1 Cleaning Mode Status BI 2 Boost Mode Status Binary Output 9 BO 0 Relay...

Страница 16: ...ture Sensor Unsigned 0 Disabled Default Mode 1 Main Control 2 Outdoor Temperature Display 3 System Networked Solutions 40108 Rin2 Underfloor Temperature Unsigned 0 Disabled default Sensor Mode 1 Min M...

Страница 17: ...d 1 Room Default Description 2 Floor 3 Outside 4 Zone 1 5 Zone 2 6 Zone 3 7 Bathroom 8 Sauna 9 Bedroom 10 Kitchen 11 Cooler 12 Flow 13 Hot Water 14 Tank 15 Pool 40140 Zone 2 Text Floor Sensor Unsigned...

Отзывы: