DeviceCommunicationControl

 

Yes

 

DM-DCC-B

 

BACnet Standard Object

 

No dynamic Creation or Deletion supported. Objects, and object instances, are assigned to fixed

 

Types Supported

 

functions within the proprietary control application of the product as follows

 

 

Object

 

Number Of

 

Instance Assignments

 

Instances

 

Device Object

 

1

 

Analog Input

 

7

 

AI(0) 

– Room Temperature

 

AI(1) - Outside Temperature

 

AI(2) - Floor Temperature

 

AI(3) - Current Active Setpoint

 

AI(4) - Humidity Measurement

 

AI(5) 

– RI1 External Sensor 1

 

AI(6) 

– RI2 External Sensor 2

 

Analogue Value

 

13

 

AV(0) 

– Not Applicable (Target SP1)

 

AV(1) 

– Not Applicable (Target SP2)

 

AV(2) 

– Not Applicable (Target SP3)

 

AV(3) 

– Not Applicable (Target SP4)

 

AV(4) 

– ECO Heating Setpoint

 

AV(5) 

– ECO Cooling Setpoint

 

AV(6) 

– Frost Setpoint

 

AV(7) 

– Min Floor Limit

 

AV(8) 

– Max Floor Limit

 

AV(9) 

– LCD Brightness

 

AV(10) - Control Hysteresis

 

AV(11) - Network Temp

 

AV(12) - Nominal Setpoint

 

Binary Input

 

3

 

BI(0) 

– Digital Input (DI1)

 

BI(1) 

– Cleaning Mode Status

 

BI(2) 

– Boost Mode Status

 

Binary Output

 

9

 

BO(0) 

– Relay Output

 

BO(1) - OFF Mode

 

BO(2) - ECO Mode

 

BO(3) 

– Light Switch Status

 

BO(4) 

– AC Switch Status

 

BO(5) 

– Lock Screen

 

BO(6) 

– Heating/Cooling Change-Over

 

BO(7) - Non Volatile Update (updates

 

setpoints/configuration parameters)

 

BO(8) - Not Applicable (Hold)

 

MutliState Input

 

2

 

MSI(0) - Device Mode (1=Comfort,

 

2=ECO, 3=OFF)

 

MSI(1) - Alarm

 

Device Object Properties

 

Property Name /ID

 

Attributes

 

Range

 

Default

 

Object Identifier

 

R/W

 

20

 

Object Name

 

R/W

 

32 Characters Max

 

Concatenation of product type and MAC

 

address i.e. "ESRT001"

 

Object Type

 

R

 

Device

 

System Status

 

R

 

STATUS_OPERATIONAL

 

Vendor Identifier

 

651

 

Model Name

 

R

 

ESRT5

 

Protocol Version

 

R

 

1

 

Protocol Revision

 

R

 

10

 

Max APDU Length

 

R

 

480

 

Segmentation Support

 

R

 

No

 

APDU Timeout

 

R

 

6000 ms

 

Number APDU Retries

 

R

 

3

 

MaxMaster

 

R

 

127

 

Max_Info_Frames

 

R

 

1

 

Database Revision

 

R

 

0

 

Содержание EIO-55 Series

Страница 1: ...EIO 55 PRODUCT MANUAL BACnet or Modbus Touchscreen Thermostat EIO 55 MOD EIO 55 BAC EIO 55 MOD HUM EIO 55 BAC HUM...

Страница 2: ...Model Type Model Description Modbus 3 5 Touchscreen Thermostat Non Programmable 24Vac dc Power Supply Non UL BACnet MSTP 3 5 Touchscreen Thermostat Non Programmable 24Vac dc Power Supply Non UL EIO 55...

Страница 3: ...000 6 1 2001 Generic Immunity EN60730 1 2016 Low Voltage EN6100 4 2 4 5 11 ESD Transient Surges Interruptions Degree of Protection IP20 Housing Housing Material Polycarbonate Plastics Self Extinguishi...

Страница 4: ...FUNCTION BASED ICON in holiday mode shows the holiday icon from where the holiday mode can be cancelled in cleaning mode shows the cleaning icon from where the mode can be can celled in BOOST mode sho...

Страница 5: ...fault the built in temperature sensor but can be configured to use an external sensor connected to RI1 The description for the room temperature can be changed via Room Text parameter in the configurat...

Страница 6: ...s the thermostat state i e if the thermostat has been switched to ECO mode via a digital input or over the network the user can cancel the mode through the touchscreen OFF Mode The thermostats can be...

Страница 7: ...ivated The lock mode can be configured to work in different ways DISABLED Lock Mode Icon Not Available ON OFF BOOST ONLY Allows On Off Boost Buttons Only ADJUST ONLY Allows Temperature Adjustment Or O...

Страница 8: ...ct closes the DI Contact Alarm alarm message is displayed on the screen Network option is selected when the digital input is used for monitoring purposes only Humidity Measurement and Display RH optio...

Страница 9: ...ol 2 Heating Cooling Change Over Min Limit Underfloor Heating Minimum Limit Setpoint 0 0 95 0 F Default 64 0 F Max Limit Underfloor Heating Maximum Limit Setpoint 0 0 122 0 F Default 86 0 F Limit Hyst...

Страница 10: ...C Enable AC Icon Network Variable 0 Disabled default 1 Enabled Enable Holiday Enable Holiday Icon 0 Disabled 1 Enabled default Humidity Display Enable Disable Humidity Display if option fitted 0 Disab...

Страница 11: ...nges are carried out over the network Modbus or BACnet then NonVol Update register object is required to be forced on to save the changes The register will automatically return to normal state when us...

Страница 12: ...Default 64 0 F Register Parameter Description Data Type Raw Data Range 104 Minimum Setpoint Unsigned 16 0 950 0 0 95 0 F Default 57 0 F 105 Maximum Setpoint Unsigned 16 0 950 0 0 95 0 F Default 86 0...

Страница 13: ...2 Override Lights Unsigned 16 0 2 0 None default 1 Override On 2 Override Off 133 Override Lock Mode Unsigned 16 0 2 0 None default 1 Lock Screen 2 Cancel Lock Mode Register Parameter Description Data...

Страница 14: ...trol 0 1 Off On Relay Output Override Relay Mode Network FUNCTION CODE 04 READ INPUT REGISTERS 0 Built In Temperature Measurement Signed 16 400 3020 40 0 150 0 C 40 0 302 0 F 1 Underfloor Temperature...

Страница 15: ...AV 9 LCD Brightness AV 10 Control Hysteresis AV 11 Network Temp AV 12 Nominal Setpoint Binary Input 3 BI 0 Digital Input DI1 BI 1 Cleaning Mode Status BI 2 Boost Mode Status Binary Output 9 BO 0 Relay...

Страница 16: ...ture Sensor Unsigned 0 Disabled Default Mode 1 Main Control 2 Outdoor Temperature Display 3 System Networked Solutions 40108 Rin2 Underfloor Temperature Unsigned 0 Disabled default Sensor Mode 1 Min M...

Страница 17: ...d 1 Room Default Description 2 Floor 3 Outside 4 Zone 1 5 Zone 2 6 Zone 3 7 Bathroom 8 Sauna 9 Bedroom 10 Kitchen 11 Cooler 12 Flow 13 Hot Water 14 Tank 15 Pool 40140 Zone 2 Text Floor Sensor Unsigned...

Отзывы: