![EasyIO EIO-55 Series Скачать руководство пользователя страница 15](http://html1.mh-extra.com/html/easyio/eio-55-series/eio-55-series_product-manual_3618763015.webp)
EIO
-55
14
DeviceCommunicationControl
Yes
DM-DCC-B
BACnet Standard Object
No dynamic Creation or Deletion supported. Objects, and object instances, are assigned to fixed
Types Supported
functions within the proprietary control application of the product as follows
Object
Number Of
Instance Assignments
Instances
Device Object
1
Analog Input
7
AI(0)
– Room Temperature
AI(1) - Outside Temperature
AI(2) - Floor Temperature
AI(3) - Current Active Setpoint
AI(4) - Humidity Measurement
AI(5)
– RI1 External Sensor 1
AI(6)
– RI2 External Sensor 2
Analogue Value
13
AV(0)
– Not Applicable (Target SP1)
AV(1)
– Not Applicable (Target SP2)
AV(2)
– Not Applicable (Target SP3)
AV(3)
– Not Applicable (Target SP4)
AV(4)
– ECO Heating Setpoint
AV(5)
– ECO Cooling Setpoint
AV(6)
– Frost Setpoint
AV(7)
– Min Floor Limit
AV(8)
– Max Floor Limit
AV(9)
– LCD Brightness
AV(10) - Control Hysteresis
AV(11) - Network Temp
AV(12) - Nominal Setpoint
Binary Input
3
BI(0)
– Digital Input (DI1)
BI(1)
– Cleaning Mode Status
BI(2)
– Boost Mode Status
Binary Output
9
BO(0)
– Relay Output
BO(1) - OFF Mode
BO(2) - ECO Mode
BO(3)
– Light Switch Status
BO(4)
– AC Switch Status
BO(5)
– Lock Screen
BO(6)
– Heating/Cooling Change-Over
BO(7) - Non Volatile Update (updates
setpoints/configuration parameters)
BO(8) - Not Applicable (Hold)
MutliState Input
2
MSI(0) - Device Mode (1=Comfort,
2=ECO, 3=OFF)
MSI(1) - Alarm
Device Object Properties
Property Name /ID
Attributes
Range
Default
Object Identifier
R/W
20
Object Name
R/W
32 Characters Max
Concatenation of product type and MAC
address i.e. "ESRT001"
Object Type
R
Device
System Status
R
STATUS_OPERATIONAL
Vendor Identifier
651
Model Name
R
ESRT5
Protocol Version
R
1
Protocol Revision
R
10
Max APDU Length
R
480
Segmentation Support
R
No
APDU Timeout
R
6000 ms
Number APDU Retries
R
3
MaxMaster
R
127
Max_Info_Frames
R
1
Database Revision
R
0