GT200 series general purpose inverter instruction manual
Parameter
code
Parameter
name
Setting range
Mini
munit
Default
value
Mod
ition
F0.07
Quick parameters
group display
selection
LED units digit
:
first parameter
display selection
0:Output frequency
(
before
compensation
)
1: Output torque
2: Setting frequency
3:Output
frequency
(
after
compensation
)
4: Bus voltage
5: AI1
6: AI2
7: Analog closed loop feedback
8: Analog closed loop setting
9: Output power
A: Output voltage
B: Output current
LED tens digit
:
second
parameter display selection
0~9:
ditto
LED hundreds digit
:
third
parameter display selection
0~9:
ditto
LED thousands digit
:
fourth
parameter display selection
0~9:
ditto
0
0x4b20
○
F0.08
Double row LED
second line
running display
parameter
selection
Display U0 group parameters
setting range:0~37
0
1
○
Basic operation parameter F1 group
F1.00
Control mode
0
:
Vector control
1
:
V/F control
1
1
×
F1.01
Run command
channel
selection
0
:
Operation panel run
command channel (LED light
on)
1
:
Terminal run command
channel (LED light off)
2
:
Serial port run command
channel (LED flickering)
1
0
○
33