GT200 series general purpose inverter instruction manual
Chapter2 Installation and Wiring of Inverter
2.1 Installation environment of inverter
2.1.1 Installation environment condition
(1) The inverter shall be installed indoors of perfect ventilation,and the
environment temperature shall be in the range of -10
℃
~40
℃,
in case that the temperature
exceeds 40
℃,
the external air-blast cooling or derating shall be used.
(2) Avoid being installed in location where suffers from the sun,dust,floatation firber and
metallic power
(3) Never to be installed in location where corrosive and explosive gas has
(4) The humidity shall be lower than 90%RH,no condensation
(5) The inverter shall be installed in the location where the plane fixed vibration is
less 5.9 m/s 2
(6) The inverter had better be kept far away from the electronmagnetic interference device
2.1.2 Installation direction and space
(1) Shall be installed vertically usually
(2) The installation space and min distance are shown as diagram2-1
(3) As shown in diagram 2-2,there shall be baffler mounted among them,when several
inverters are installed vertically.
B
Fan efficiency exhaust
B
A
A
PRG
M-F
ENT
RUN
STOP
RESET
Hz
A
V
RUN
MON
QUICK
REV/FWD
Guide plate
in
v
er
ter
in
v
er
ter
Diagram2-1 Installation space
Diagram
2-2 Installation of multi inverters
13