GT200 series general purpose inverter instruction manual
Address
Function
Code
Register
Address
Register
Number or
Read bytes
Register
Content
Checksum
0x05
0x03
0x3306
0x0001
None
0x6ACB
0x045
0x03
None
0x02
0x12C
0x49C9
Read 5#inverter’s decelerating time (which is F0.11), and inverter response decelerating
time is 6.0S.
Address
Function
Code
Register
Address
Register
Number or
Read bytes
Register
Content
Checksum
0x05
0x03
0x000B
0x0001
None
0xF4C4
0x05
0x03
None
0x02
0x003C
0x4995
Inverter’s scaling relationship
A) Frequency’s scaling is 1: 100
To make the inverter rotate at 50Hz, the main setting should be 0x1388 (5000).
B) Time’s scaling is 1: 10
To make the inverter accelerating time as 30S, the function code should be set to 0x012c
(300).
C) Current’s scaling is 1: 10
If the inverter’s feedback current is 0x012c, current of this inverter is 30A.
D) Output power is an absolute value.
F) Others (i.e. terminal input and output etc.) Please refer to the inverter’s user manual.