Eagle Eye GD-3000 User Manual
2.2 Do Not Use For
The Eagle Eye GD-3000 Combustible Gas Detector is
NOT
intended for use in
hazardous locations or industrial applications such as refineries, chemical plants, etc.
DO NOT
mount the Eagle Eye GD-3000 Combustible Gas Detector where the normal
ambient temperature is below 0°F or exceeds 125°F (-18°C or above 52°C). The GD-
3000 Combustible Gas Detector mounts on a type 4S electrical box supplied by the
contractor.
WARNING
The Eagle Eye GD-3000 Combustible Gas Detector may not function effectively below
0°F or above 125°F (-18°C or above 52°C). Using the detector outside of this
temperature range may adversely affect product performance and
result in
sickness
or death.
2.3 General Description
The Eagle Eye GD-3000 Combustible Gas Detector is a low voltage, dual relay
combustible gas (EX) detector and automatic ventilation controller. The GD-3000
Combustible Gas Detector uses a microcomputer controlled, electronic system to
measure the concentration of combustible gas, actuate relays and provide a 4-20mA (0-
50% LEL) output. The GD-3000 Combustible Gas Detector is low maintenance with a
long life (5+ years) pellistor sensor and optional gas test and calibration kits. The GD-
3000 Combustible Gas Detector is a low level meter capable of displaying from 0-50%
LEL of combustible gas.
Features
• ETL Listed to UL 61010-1
• The Eagle Eye GD-3000 Combustible Gas Detector can be bump-tested with the FTK
with 10% LEL Methane, 10% LEL Propane or 10% LEL Hydrogen gas, regulator and
calibration hood.
• The GD-3000 Combustible Gas Detector can be field calibrated using 10% LEL
Methane, 10% LEL Propane or 10% LEL Hydrogen gas, regulator and calibration hood.
• The GD-3000 Combustible Gas Detector is a low level meter capable of displaying
from 0-50% LEL EX
• Selectable fan and alarm relay activation
• 5A SPDT fan relay controls starters of exhaust fans
• 0.5A N.O. or N.C. alarm relay connects to warning devices or control panels
• 4-20mA current loop
5