Eagle Eye GD-3000 User Manual
There are multiple ways to test the Eagle Eye GD-3000 Combustible Gas Detector after
installation: Operation Test, Manual Operation Test, Combustible Gas Test and Quick
Gas Test. The GD-3000 Combustible Gas Detector also has the ability to test itself
automatically and does so every 2 1/2 minute cycle. If the unit detects an improper
voltage or inoperable component it will default into Error mode. In Error mode, the unit
will Flash Green and both the fan & alarm relay will be actuated. Check that the GD-
3000 Combustible Gas Detector OPERATING LED type light is illuminated,
continuously. If not, do not proceed with the tests. If the unit is in error mode contact
your local representative Eagle Eye technical support.
4.2.1 Operation Test
1. Remove the single screw in the middle of the front cover of the Eagle Eye GD-3000
Combustible Gas Detector.
2. Remove the front cover.
3. Observe the LED light on the front of the Eagle Eye GD-3000 Combustible Gas
Detector.
4. If the light is solid green proceed to step 6.
5. If the light is off or flashing Green, refer to the General section of this
User Instruction.
6. Locate the switch labeled ENTER/TEST on the left side of the printed circuit board.
Press the Test switch once.
7. The Eagle Eye GD-3000 Combustible Gas Detector will step through a cycle test:
a. The display progresses through the
Art
(alarm relay test),
Frt
(fan relay test) then
42t
(4-20mA output test).
b. During the first 5 seconds of the test cycle, the alarm relay will be closed, so any
devices connected to that relay will be tested.
c. The Fan relay will be activated for the next 1 minute of the test, so if the fan circuits
are wired in the normal manner,
the fan should run.
d. The 4-20mA output will then ramp up from 4 to 20mA over the next 130 seconds of
the test, so if the circuit is wired
in the normal manner, the control panel or building automation system should respond.
e. At the end of the test cycle, the light will turn green and be on steady (Normal
Operation), the fan & alarm relay will be
in standby mode and the 4-20mA output will return to 4mA (in clean air).
8. When testing is completed reassemble the unit or units.
4.2.2 Manual Operation Test
This option gives the user the opportunity to manually initiate an individual test for each
relay, the analog output and the sensor response to gas. From normal operation mode
17