Eagle Eye GD-3000 User Manual
press the
Next
button 3 times to get to the Test Mode (tSt). Press the
Enter
button once
to get into the Test Menu. Press the
Next
button to scroll through the four test options
and press
Enter
to initiate the selected test. Note that if the relay or 4–20mA output has
been disabled, the test selection will not be displayed in the test menu.
Art - Alarm Relay Test, 10 seconds
Frt - Fan Relay Test, 60 seconds
42t - 420 loop test, 25 seconds
gtS - Gas Test, 3 minutes (no output to the panel during the gas test)
The display will flash during the test or in the case of the gas test the level will alternate
with the expected gas (
mE
,
Pro
or
Hy
).Once the test is complete, the display will return
to steady display. To exit the test menu, press the
Next
button until “End” is displayed
then press
Enter
to return to normal mode.
4.2.3 Combustible Gas Test
The following steps must be performed when conducting a calibration or calibration
verification test (bump test) to ensure proper performance of the monitor. Failure to do
so may adversely affect product performance and
result in sickness or
death.
• When performing a calibration or calibration verification test (bump test) only use
certified calibration gas at the required concentration level. Do not calibrate with expired
calibration gas.
• If the instrument cannot be calibrated, do not use until the reason can be determined
and corrected.
• Do not cover or obstruct display, audible alarm opening or visual alarm cover.
• Ensure sensor inlet is unobstructed and is free of debris.
General
The Eagle Eye GD-3000 Combustible Gas Detector can be bump-tested or calibrated
with a Field Calibration Kit (FCK) with Methane, Propane or Hydrogen gas, regulator
and test hood, available through your local representative or from Eagle Eye.
FCK Information
Several detectors can be calibrated with one FCK. The only limitation is the amount of
gas in the cylinder. The 17 liter cylinder with 0.2 LPM (Liters Per Minute) regulator has
approximately 85 minutes of continuous calibration run time. Replacement cylinders are
18