FF47
65351 Device type dif
Reaction 1: Downramp actual
speed; remain in position
control state.
Check feedback cable for EMC conform wiring (correct screening),
reduce EMC emissions in the environment (is the motor screened, is
the system correctly grounded etc.), reduce line length. Select a
memory range for the memory access via objects.
FF48
65352
BDM configuration
download is not
possible
Reaction 1: Downramp actual
speed; remain in position
control state.
Check feedback cable for EMC conform wiring (correct screening),
reduce EMC emissions in the environment (is the motor screened, is
the system correctly grounded etc.), reduce line length. Check clock
and data lines for breakages and for contact problems
With new model (ID 0000811814_52) of Parker SBC motor
feedback variant B9 (EnDat EQI 1331) this error was also triggered
accidently because of a firmware bug. Error is fixed with Firmware
Release >=R09-42.
FF49
65353 Irregular device state
Reaction 1: Downramp actual
speed; remain in position
control state.
Check feedback cable for EMC conform wiring (correct screening),
reduce EMC emissions in the environment (is the motor screened, is
the system correctly grounded etc.), reduce line length.
FF4A
65354 SCI_FBI Timeout error
Reaction 1: Downramp actual
speed; remain in position
control state.
Avoid the listed error sources. The error might also be given if there
is a problem with the feedback cable (e.g. bad Clock signal
connection).
FF4B
65355
Insufficient memory
for IEC program
Reaction 1: Downramp actual
speed; remain in position
control state.
Exchange or have feedback system repaired.
FF4C
65356 IEC: object not found
Reaction 1: Downramp actual
speed; remain in position
control state.
Switch on Compax3 (24V supply) with EnDat with a lower speed or
at standstill.
FF4D
65357 IEC: Version conflict
Reaction 1: Downramp actual
speed; remain in position
control state.
Check cable, connect EnDat feedback or configure the "right"
desired feedback.
FF4E
65358
Not enough memory
for configured Scope
settings available
Reaction 1: Downramp actual
speed; remain in position
control state.
Connect EnDat2.2 feedback device or configure feedback as
EnDat2.1 feedback (with incremental signals) (Motor manager).
FF50
65360 HEDA Sync error
Reaction 1: Downramp actual
speed; remain in position
control state.
Operate EnDat feedback device if possible (cable, feedback type)
with incremental signals (configuration in the Motor Manager),
replace feedback device by a compatible type.
FF51
65361 HEDA timeout error
Reaction 1: Downramp actual
speed; remain in position
control state.
Do not attempt access or contact our technical support.
FF52
65362 No HEDA Master
Reaction 1: Downramp actual
speed; remain in position
control state.
Exchange feedback.
FF60
65376 CANopen library
Reaction 1: Downramp actual
speed; remain in position
control state.
Exchange feedback.
FF61
65377
CANopen
confirmation
Reaction 1: Downramp actual
speed; remain in position
control state.
Exchange feedback.
FF62
65378 No CANopen master
Reaction 1: Downramp actual
speed; remain in position
control state.
Exchange feedback.
FF70
65392
EnDat: Internal alarm
"illumination"
Reaction 2: Downramp /
apply brake / de-energize..
Exchange feedback.
FF71
65393
EnDat: Internal alarm
"signal amplitude"
Reaction 2: Downramp /
apply brake / de-energize..
Exchange feedback.