6310

25360 Checksums

Reaction 1: Downramp actual 
speed; remain in position 
control state.

If the software end limits are exceeded: Check set value default, end 
limits and referencing, bring axis back into permissible range. 
Invalid target position: Limit target position to the permissible 
travel range.
In order to avoid the error message (not recommended in general, 
but absolutely necessary in endless applications with reset distance) 
assign True to the "Disable_SoftwareLimit_Pos" input of the 
"C3_ErrorMask" IEC module, call up the "C3_SetErrorReaction" IEC 
module with ErrorID "29475" and Reaction "0" (no reaction, error is 
deactivated) or deactivate the function in the configuration.
Firmware update to release version higher than R07-1, if error 
during manual travel.

7113

28947

C3 PSUP: Short circuit 
of braking resistor

Reaction 1: Downramp actual 
speed; remain in position 
control state.

If the software end limits are exceeded: Check set value default, end 
limits and referencing, bring axis back into permissible range. 
Invalid target position: Limit target position to the permissible 
travel range.
In order to avoid the error message (not recommended in general, 
but absolutely necessary in endless applications with reset distance) 
assign True to the “Disable_SoftwareLimit_Neg" input of the 
"C3_ErrorMask" IEC module, call up the "C3_SetErrorReaction" IEC 
module with ErrorID "29476" and Reaction "0" (no reaction, error is 
deactivated) or deactivate the function in the configuration.
Firmware update to release version higher than R07-1, if error 
during manual travel.

7121

28961 Motor Stall occurred

Reaction 2: Downramp / 
apply brake / de-energize..

If the software end limits are exceeded: Check set value default, end 
limits and referencing, bring axis back into permissible range.
Invalid target position: Limit target position to the permissible 
travel range.
In order to avoid the error message, deactivate the positive end 
limit error in the configuration or in the IEC program (not 
recommended).
Firmware update to release version higher than R07-1, if error 
during manual travel.

7180

29056

Motor pulse usage 
too high (i²t)

Reaction 2: Downramp / 
apply brake / de-energize..

If the software end limits are exceeded: Check set value default, end 
limits and referencing, bring axis back into permissible range.
Invalid target position: Limit target position to the permissible 
travel range.
In order to avoid the error message, deactivate the negative end 
limit error in the configuration or in the IEC program (not 
recommended).
Firmware update to release version higher than R07-1, if error 
during manual travel.

7181

29057

Line breakage motor 
temperature 
monitoring

Reaction 1: Downramp actual 
speed; remain in position 
control state.

Increase deceleration and deceleration jerk, execute following 
movement earlier (from a smaller speed or with a longer distance 
to the following movement). As from R07-3, it is possible to activate 
option “permit higher deceleration for RegMove” in the 
configuration of reg-related positioning with T11, in order to avoid 
the error.
If (with T30/T40) the monitoring is not desired, object 1111.17 must 
be set to zero.

Содержание MDSF

Страница 1: ...22 E H Wachs All rights reserved This manual may not be reproduced in whole or in part without the written consent of E H Wachs E H Wachs 600 Knightsbridge Parkway Lincolnshire IL 60069 www ehwachs co...

Страница 2: ...MDSF Servo Electric Drive 69 SERVO MAN 01 E H Wachs Company...

Страница 3: ...tains instructions and illustra tions Use these instructions to perform the machining oper ation The narrower column on the outside contains additional information such as warnings special notes and d...

Страница 4: ...may result in damage to the equipment A NOTE provides supple mentary information or oper ating tips Read and follow all safety guidelines and instructions in the manual for your MDSF or EP 424 machin...

Страница 5: ...with on off switch and electronic error code display panel electric drive motor assembly with adapter for mounting to MDSF pinion housing control pendant with start stop speed control and emer gency s...

Страница 6: ...ic Drive Specifications Power Requirements 380 480 VAC 50 60 Hz Component Weights Power cabinet 40 8 lb 18 5 kg Motor assembly with cable 40 2 lb 18 3 kg Pendant with cable 2 6 lb 1 2 kg Cable lengths...

Страница 7: ...the MDSF pinion assembly Use a lifting device if necessary the drive motor assembly has a lift handle Insert the motor drive shaft all the way into the pin ion spline engaging the face gear Snap the...

Страница 8: ...ntrol cabinet Connect it to the back of the control cabinet NOTE Do not plug the power cable into the elec trical source until you have the machine and drive mounted and ready to operate 2 Connect the...

Страница 9: ...or cover OPERATING INSTRUCTIONS Using the Control Pendant The control pendant is enabled when the electrical system is powered on When not operating the drive push in the Emergency Stop button to prev...

Страница 10: ...Releasing the trigger will stop the motor to re start hold the trigger and press the Start button Operating the Drive 1 Make sure the cables are connected to the control cab inet power source motor p...

Страница 11: ...button on the pendant See pendant operating instruction in the previous sec tion 6 Turn the power switch on the front of the cabinet to the ON position Figure 1 8 Turn the power switch to the ON posi...

Страница 12: ...trigger to stop the machine 13 If necessary press the Emergency Stop button on the pendant to immediately stop the machine and disable power 14 Always press in the Emergency Stop button when making a...

Страница 13: ...Error Codes The LED display on top of the control cabinet displays error codes when there is an error condition Appendix A lists and describes the error codes Figure 1 10 The LCD screen on top of the...

Страница 14: ...MDSF Servo Electric Drive 12 Part No 69 SERVO MAN 01 Rev A E H Wachs APPENDIX A ERROR CODE REFERENCE...

Страница 15: ...Speed control Stiffness and or damping set too high too high signal delay in the control loop current bandwidth too small 50 control signal or actual speed value filter 1 and 2 set too high control l...

Страница 16: ...f you wish to operate Compax3 with a lower DC bus voltage 70V mask this error As from Release 05 this can be achieved in the configuration via IEC T30 T40 with the error module C3_ErrorMask or with th...

Страница 17: ...Reaction 2 Downramp apply brake de energize Verify external wiring 4310 17168 Motor Temperature Reaction 2 Downramp apply brake de energize Verify wiring and power supply unit 4410 17424 C3 PSUP Devi...

Страница 18: ...remain in position control state Caution The safety of the STO safety function is no longer guaranteed Please check external wiring Error cannot be acknowledged when the error is eliminated the 24V mu...

Страница 19: ...et cycle time in the IEC download dialog refrain from using time intensive processes for example saving objects in Flash 5F48 24392 Effective motor usage too high i t Reaction 2 Downramp apply brake d...

Страница 20: ...sed by positiv controller feedback in speed control loop check motor commutation from within MotorManager If it is not correct there might be the following causes wrong motor wiring Phases swapped shi...

Страница 21: ...configuration Firmware update to release version higher than R07 1 if error during manual travel 7121 28961 Motor Stall occurred Reaction 2 Downramp apply brake de energize If the software end limits...

Страница 22: ...he position difference will accumulate Resetting is possible by writing 1 into C3Plus LoadControl_Command O2201 2 as well as by a homing run also Teaching of the drive As an alternative position diffe...

Страница 23: ...heck hall wiring and verify function of hall sensors If needs be eliminate EMC disturbance on hall signals e g improve motor cable shielding optimize signal lead of the hall signals in the case of an...

Страница 24: ...gize Increase starting current O2190 2 and eliminate very high direction dependence or friction if any Check feedback resolution and or number of feedback or motor poles With a high inertia or mass to...

Страница 25: ...e force controller of the auxiliary axis 73A8 29608 Automatic commutation No standstill during phase 3 Reaction 2 Downramp apply brake de energize Increase configured maximum pressure check maximum pr...

Страница 26: ...e Compax3 O3921 3 or O3921 10 and O3921 2 or O3921 9 or output modulo of the controller 73D1 29649 Tracking error Force control aux Axis Reaction 1 Downramp actual speed remain in position control sta...

Страница 27: ...eaction 2 Downramp apply brake de energize 7489 29833 Cam generator reserved Reaction 1 Downramp actual speed remain in position control state The error occurs for example if the response times of the...

Страница 28: ...ntrol state Select valid coupling segment O3011 3 or verify curve memory 7590 30096 HEDA synchronization error Reaction 2 Downramp apply brake de energize Select valid segment or verify curve memory 7...

Страница 29: ...ect correct machine zero mode check reference point initiators feedback zero cable voltage supply feedback type debounce reversal switches via software debounce time reduce acceleration for reversal v...

Страница 30: ...rved Reaction 2 Downramp apply brake de energize 819e 33182 CamCommand reserved Reaction 2 Downramp apply brake de energize 81F0 33264 CAN Bus inactive status Reaction 1 Downramp actual speed remain i...

Страница 31: ...y without ramp application of the brake output error number system restart software reset FE08 65032 Exception 08 DSP System Switch off of the current immediately without ramp application of the brake...

Страница 32: ...than R08 1 for very old devices firmware V01 xx yy FF13 65299 Timeout error Reaction 1 Downramp actual speed remain in position control state FF14 65300 Overflow error Reaction 1 Downramp actual speed...

Страница 33: ...environment is the motor screened is the system correctly grounded etc reduce line length FF41 65345 Power fail safe data are invalid Reaction 1 Downramp actual speed remain in position control state...

Страница 34: ...te Exchange or have feedback system repaired FF4C 65356 IEC object not found Reaction 1 Downramp actual speed remain in position control state Switch on Compax3 24V supply with EnDat with a lower spee...

Страница 35: ...ation Reaction 1 Downramp actual speed remain in position control state Exchange feedback FF83 65411 EnDat Internal warning battery charge Reaction 1 Downramp actual speed remain in position control s...

Страница 36: ...main in position control state Update Compax3 firmware FFA1 65441 SinCos Analog signals beyond specification Reaction 2 Downramp apply brake de energize Ensure that the motor is at a standstill FFA2 6...

Страница 37: ...server reduce HEDA mapping objects contact technical support FFAC 65452 SinCos number of transmitted data is faulty Reaction 2 Downramp apply brake de energize Maybe a SineCosine encoder is operated i...

Страница 38: ...FBE 65470 SinCos feedback temperature approaching limit Reaction 2 Downramp apply brake de energize FFBF 65471 SinCos speed exceeds normal no position generation permitted Reaction 2 Downramp apply br...

Страница 39: ...bandwidth When working with high motor speed and operation at the voltage limit make sure you use a release 2004R03 Firmware and PC Software With older firmware versions the error may be reported in c...

Страница 40: ...ystem Error 2 Reaction 2 Downramp apply brake de energize FFEC 65516 FBK System Error 3 Reaction 2 Downramp apply brake de energize FFED 65517 FBK System Error 4 Reaction 2 Downramp apply brake de ene...

Страница 41: ...l state FFFB 65531 User error 11 Reaction 1 Downramp actual speed remain in position control state FFFC 65532 User error 12 Reaction 1 Downramp actual speed remain in position control state FFFD 65533...

Страница 42: ......

Отзывы: