22 of 105
The GSC400 also has a dedicated
emergency stop
input that when open will stop the
generator immediately and the controller will enter the OFF Mode (see below for more
information on the OFF Mode) and remain in the OFF Mode until the emergency stop
input is grounded. While the emergency stop input is active the GSC400 will sound an
audible alarm and display “Emergency Stop” on the LCD display. See Figure 4 on page
15 for the location of the emergency stop input.
5.3
Controller States
The GSC400 incorporates 3 primary modes of operation:
1.
OFF Mode
2.
AUTO Mode
3.
RUN Mode
1.
OFF Mode – When the GSC400
is set to the Off Mode, automatic
starting will be disabled. No
automatic controls will be
initiated. The Off Mode may be
initiated when no generator
controls are required or when the
controller configuration requires
adjustment. The user can disable
manual start in OFF mode in the
basic menu. See section 5.9.2.
All of the failures and most of t
Off Mode. The controller will beep every few seconds to alert the user that the
unit is in the Off Mode and cannot automatically start. To silence this alarm press
the off key as instructed on the screen.
he warnings are disabled when the controller is in
Off Mode you may simultaneously press the up and down arrow keys to
.
AUTO Mode - When the
Mode,
nclude
and
hich
,
In
perform a lamp test.
2
GSC400 is set to the Auto
automatic starting will be
enabled. Possible triggers i
start/stop, battery recharge
exerciser features (all of w
are controllable from the menu
system). If the engine is started
failures will be automatically
detected allowing for safe engine
operation.
Содержание GSC400 Series
Страница 15: ...Figure 4 General GSC400 System Wiring Diagram ...
Страница 16: ...Figure 5 Digital IO Example ...
Страница 104: ...104 of 105 12 Appendix D Additional Drawings The follow pages include various drawings that may be of benefit ...