15 LOW BATTERY
16 LOW COOLANT
17 OVER CRANK
18 OVER VOLTAGE
19 UNDER VOLTAGE
20 OVER CURRENT
21 EPS LOADS ERROR
22 LOW AIR PRESSURE
23 LOW HYDRAULIC
24 LOW OIL LEVEL
25 LOCKED ROTOR
26 HIGH BATTERY
27 LOSS OF ECM COMMUNICATION
28 OPEN ENG TEMP (applies to both
High and Low Engine Temperature)
29 SHORT ENG TEMP (applies to both
High and Low Engine Temperature)
30 OPEN OIL PRES
31 SHORT OIL PRES
32 OPEN FUEL LEVEL
33 SHORT FUEL LEVEL
34 OPEN OIL LEVEL
35 SHORT OIL LEVEL
36 OPEN FUEL BASIN
37 SHORT FUEL BASIN
40 AUXILIARY FAIL
41 UNDER FREQUENCY
42 OVER FREQUENCY
162 USER CONFIG FAIL 1
163 USER CONFIG FAIL 2
255 (0xFF) Empty – No failure message
40109
System Sub-state
delay countdown
0 ~ 65535
R
The value of register 40109 corresponds to
the count down delay for one of the below
mentioned sub-states. To determine which
sub-state is in countdown mode read
register 40101. Resolution is 1 second.
The following sub-states incorporate delay
countdown:
DLY TO START
PREHEATING