47 of 105
Oil Level
Input Pin
Reserve, Analog 2-7
Signal Source
J1939, Switch input, Sender
Bypass Delay
10-60 Seconds
Switch Setting
GND = Fail, Open = Fail
Shorted Sender
Disable, Warning, Shutdown
Open Sender
Disable, Warning, Shutdown
Units
Percentage
Warning Level
0-100%
Failure Level
0-100%
Fuel In Basin
Input Pin
Reserve, Analog 2-7
Signal Source
J1939, Switch input, Sender
Bypass Delay
10-60 Seconds
Switch Setting
GND = Fail, Open = Fail
Shorted Sender
Disable, Warning, Shutdown
Open Sender
Disable, Warning, Shutdown
Units
Percentage
Warning Level
0-90%
Failure Level
0-90%
Low Engine Tmp
Input Pin
Reserve, Analog 2-7
Signal Source
J1939, Switch input, Sender
Bypass Delay
10-60 Seconds
Switch Setting
GND = Fail, Open = Fail
Shorted Sender
Disable, Warning, Shutdown
Open Sender
Disable, Warning, Shutdown
Units
Fahrenheit, Celsius
Warning Level
10-265°F, 10-265°C
Speed Sensing
Signal Source
J1939, Mag pickup, Gen output
Rated Freq
10-9990 Hz
Rated RPM
200-4000 RPM
Over RPM Warn
100-5000 RPM
Over RPM Fail
100-5000 RPM
Under RPM Warn
100-5000 RPM
Under RPM Fail
100-5000 RPM
AC Frequency
DisconnectFreq
1-100 Hz
Over Freq Warn
1-100 Hz
Over Freq Fail
1-100 Hz
UnderFreq Warn
1-100 Hz
UnderFreq Fail
1-100 Hz
A/C Voltage
Voltage Source
Disable, Enable
Voltage Display
Line-Line, Line-Neutral, Both
Voltage Group
1-Single, 2-Three, 3-Hi Wye, 4-Three
phase
Group 1 Setting
3 Wire Single, 2 Wire Single
Group 4 Setting
Four Wire Delta, Three Phase
Over Volt Warn 1
0-700 VAC
Over Volt Fail 1
0-700 VAC
Under Volt Warn 1
0-700 VAC
Under Volt Fail 1
0-700 VAC
Over Volt Warn 2
0-700 VAC