47 Low Speed Warn
48 Locked Rotor
49 Fuel In Basin
50 Low Battery
51 High Battery
52 AUTO FOR SILENCE
53 AUTO FOR ALARM
54 Low Engine Temperature warning
55 Open Engine Temperature sender
56 Short Engine Temperature sender
57 Open Oil Pressure sender
58 Short Oil Pressure sender
59 Open Fuel Level sender
60 Short Fuel Level sender
61 Open Oil Level sender
62 Short Oil Level sender
63 Open Fuel Basin sender
64 Short Fuel Basin sender
70 EMERGENCY STOP
71 Auxiliary Warn
72 Under Frequency warning
73 Over Frequency warning
255 (0xFF) Empty – No message in queue
40108
Active Failure
0 ~ 44
R (Read
Only)
If the controller is in an active FAILURE
mode the failure number in register 40108
corresponds to the below failure mode.
0 reserved
1 Internal reserved 1 ( ADE Read )
2 Internal reserved 2 ( KEYBOARD )
3 Internal reserved 3 ( ADC read )
4 Internal reserved 4 ( RS485 )
5 Internal reserved 5 ( RS232 )
6 Internal reserved 6 ( ADE Write )
7 Internal reserved 7 ( TLE6230 )
8 Internal reserved 8 ( EEPROM )
9 (Reserved )
10 HIGH ENGINE TEMP
11 LOW OIL PRESSURE
12 UNDER SPEED
13 OVER SPEED
14 LOW FUEL LEVEL