SmartVue Operator’s Manual
10-0004-R13
119
21.3 Power and Signal Connections
Power and input/output connections are made through four removable terminal blocks on
the back of the SmartVue (Figure 21-5). The terminal assignments are listed in Table
21-1.
Figure 21-5 Rear view of the SmartVue with terminal block layout
Each terminal block can be removed without having to disconnect any wires that may
already be secured to the terminals. To remove a terminal block use a small slotted
screwdriver to loosen the two screws on both ends, then pull the connector socket away
from the terminal pins.
Table 21-1 SmartVue Terminal Block Pinout
Connector
Terminal
Label
Description
J1
1
0-10V OUT 2
0-10 V output 2 (100
Ω
, 10 mA max.)
2
0-10V OUT 1
0-10 V output 1 (100
Ω
, 10 mA max.)
3
ISOLATED 24V -
24 V supply (negative)
4
ISOLATED 24V +
24 V supply (positive)
5
4-20mA OUT 2-
14-bit analog isolated output 2 (negative)
6
4-20mA OUT 2+
14-bit analog isolated output 2 (positive)
7
4-20mA OUT 1-
14-bit analog isolated output 1 (negative)
8
4-20mA OUT 1+
14-bit analog isolated output 1 (positive)
9
4-20mA IN 2-
16-bit analog input 2 (negative)
10
4-20mA IN 2+
16-bit analog input 2 (positive)
11
4-20mA IN 1-
16-bit analog input 1 (negative)
12
4-20mA IN 1+
16-bit analog input 1 (positive)