4

CLEARANCE

Allow at least a 2-inch clearance between  

DuraPlus Pipe and any combustible materials.  

Where the chimney passes through floors, 

joists, or ceilings, Firestop Radiation Shields,  

Support Boxes, and Close Clearance Shields 

may permit reduced clearances as established 

by these parts, or spacers built on to these 

parts.  The clearance (air space) between 

the outer chimney wall, and the inside of the 

Support Box,  Firestop Radiation Shields,  

and Close Clearance Shields, in the cases 

of 7 and 8-inch diameter chimney will be less 

than 2 inches.  Both of these systems have 

been extensively tested and evaluated at 

these clearances.  This reduced clearance is 

permissible at these internal locations only.  

All other areas require a 2-inch minimum 

clearance.  Never fill any required clearance 

space with insulation or any other materials.  

Combustible materials include lumber plywood, 

sheetrock, plaster and lath, furniture, curtains, 

electrical wiring and building insulation.  Keep 

single wall stovepipe at least 18 inches 

away from combustible materials, unless a 

clearance reduction system that is acceptable 

to the authority having jurisdiction is used, or 

the appliance to be installed is listed and the 

instructions specify a different clearance.

PERMITS 

Contact your local Building Official or Fire 

Official regarding permits, restrictions, and 

installation inspections in your area.  

DURAPLUS APPLICATIONS 

Use DuraPlus with wood stoves, fireplaces, 

furnaces, boilers, water heaters, stoves, 

ranges, or other residential-type appliances 

fueled by oil, gas, coal, or wood.  Do not use 

with forced draft positive-pressure appliances.  

DuraPlus systems are designed to extend 

vertically with a maximum of (2) offsets of 30° 

(offset and return).  DuraPlus is tested to UL 

Test Proceedure 103HT, and listed under UL 

Re-examination Service Number MH7399.

Tools You May Need

Hammer  Level    

 

 

Caulking Gun 

Plumb Bob 

Screwdriver 

Tin Snips 

Saber or Keyhole Saw 

Drill

 

Materials You May Need 

Non-hardening Waterproof Sealant

8 Penny Nails  

 

 

 

5/16 inch x 3 inch long Lag Screws  

Roofing Nails  

 

 

3/4 inch Galvanized Electrical Conduit (where 

the chimney extends 4 feet or more above the 

roof) 

Safety Equipment 

Dependable Ladder  

Eye Protection  

 

 

 

Proper Gloves  and Shoes 

INSTALLATION NOTES

 

Proper planning for your  DuraPlus installation 

will result in greater safety, efficiency, and 

convenience, as well as saving time and 

money.  Use only authorized DuraPlus (SDP) 

listed chimney parts.  You must use 100% 

DuraPlus listed parts to obtain a DuraPlus 

listed system.  Do not mix parts or try to 

match with other products, or use improvised 

solutions.  Do not install damaged parts. 

 Table 

1

 lists the authorized components, and their 

respective Underwriter’s Laboratory Catalog 

Содержание duraplus

Страница 1: ...DuraPlus All Fuel Chimney System Installation Instructions...

Страница 2: ...manufacturer s warranty and may have an effect on your homeowner s insurance and UL listing status Keep these instructions for future reference This booklet also contains instructions for installing a...

Страница 3: ...7 Offset Elbow Installation 12 Offset Chart 13 Extended Roof Bracket Installation 14 Roof Supported Installations 15 Tee Supported Installations 16 Masonry Fireplace Installations 18 Zero Clearance Fi...

Страница 4: ...ct your local Building Official or Fire Official regarding permits restrictions and installation inspections in your area DuraPlus APPLICATIONS Use DuraPlus with wood stoves fireplaces furnaces boiler...

Страница 5: ...building within ten feet Figure 1 DuraPlus may be installed up to 35 feet high If a chimney is installed higher than 35 feet a supporting Elbow Strap must be placed every 8 feet If the chimney extend...

Страница 6: ...elow pertain to all stoves or other appliances installed with DuraPlus chimney systems Choice Choose a stove that is listed by a recognized testing laboratory is appropriate for your needs and is not...

Страница 7: ...and mark this center point on the ceiling Refer to Table 2 for specific framing and clearance dimensions Mark appropriate cutting lines around the center point Cut a square hole in the ceiling for a...

Страница 8: ...passes through additional floors and ceilings install Firestop Radiation Shields Where the chimney passes through an attic Firestop Radiation Shields and Insulation Shields must be installed 4 Frame O...

Страница 9: ...tibles is not required when the chimney passes through Close Clearance Shields When using Close Clearance Shields Ventilated Flashing must be installed Refer to Figure 10 which pictures both Ventilate...

Страница 10: ...outer liner 8 Install Attic Insulation Shield Install the Attic Insulation Shield where the chimney passes into an attic It s purpose is to prevent debris and insulation from getting too close to the...

Страница 11: ...ermit sliding the next Chimney Section up through the Flashing Always insure the chimney remains vertical and that at least a 2 inch clearance to combustible materials is maintained all around Install...

Страница 12: ...t furnished by DuraVent 11 Enclosures Enclose chimneys where they pass through occupied spaces including closets Always maintain at least a 2 inch clearance between the chimney and any combustible sur...

Страница 13: ...s band around the angled portion of the top Elbow then tighten the nut and bolt until the clamp is firm Wrap the Elbow Strap end over an adjacent joist or rafter and secure it with at least two 8 pen...

Страница 14: ...il heads carefully with a non hardening waterproof sealant 3 Attach Conduit Flatten 1 inch and drill a 1 4 inch hole at each end of both pieces of conduit Bolt each conduit to the Pipe Band and Roof B...

Страница 15: ...from combustibles etc 2 Cut Openings Cut a roof opening directly above the appliances flue outlet collar just as in a Ceiling Supported Installation Steps 1 thru 5 If a separate ceiling and roof exis...

Страница 16: ...e s flue outlet collar For new construction prior to sheetrock or other covering of the wall studs is applied frame a square opening between the studs as specified in Table 2 Figure 25 Should it be ne...

Страница 17: ...tion of wall thimble sdp wt black outside view from outside Figure 27 note if system exits thru wall into garage an enclosure isrequired ventilated flashing must be used 2 inches minimum enclosure GAR...

Страница 18: ...enclosure has been constructed installing the chase cover requires some special considerations The chase must be ventilated at the top and a 1 2 inch air gap must be established between the cover and...

Страница 19: ...10 Refer to Figure 1 and Table 4 for chimney height requirements Always maintain at least 2 inches of clearance to combustible materials and enclose the chimney where it passes through occupied areas...

Страница 20: ...20 Table 4...

Страница 21: ...ip connector slips into the hole in the ceiling support or wall thimble Align the tabs on the slip connector with the notches in the face of the support or wall thimble push the connector in and twist...

Страница 22: ...leaning unscrew the four screws that attach the cap s support legs to the cap base The Tee Cleanout Cap can be removed once the screws are unscrewed Remember to replace the cap when you are finished c...

Страница 23: ...23...

Страница 24: ...case of a chimney fire the chimney must be inspected and approved by a certified Chimney Sweep before reuse After each annual inspection maintenance and cleaning the certified Chimney Sweep must fill...

Отзывы: